© Danfoss | DCS (az) | 2018.02
06
7R
960
8
06
7R
960
8
1
2
3
1
2
3
Installation guide
Thermostatic expansion valves
Type TE 5, TE 12, TE 20 and TE 55
DKRCC.PI.A00.C6.02 | 1
Max. test pressure P
test
:
32 bar / 465 psig
Min. 5% Ag
TE12 tight torque =
45 ± 5 Nm / 33 ±3.7 ft-lbs
Allen key M6
Type
Torque ± 5%
Nm
kpm
ft-lbs
TE 5
10
1.1
7.4
TE 12
13
1.4
9.6
TE 20
13
1.4
9.6
TE 55
15
1.6
11.1
Max. working pressure PS / MWP:
28 bar / 400 psig
Refrigerants:
R407F, R407A, R448A, R449A, R452A, R513A,
R404A, R507, R22, R134a and R407C.
For complete list of approved
refrigerants, go to www.danfoss.com
Solder
Flange
Torx T25
Max. 4Nm
(3ft-lbs)