Parameter lists
A.4 Meter setup
SONO 3500 CT
Operating Instructions, 07/2019, VI.SH.P2.02
81
Parameter
Default
value
Value
range
Access
level
Description
543
Actual battery capacity
25.000000 0 ... 50
R/W**
The capacity of the battery in Ah
- Single 12.5 Ah
- Dual battery pack 25.0 Ah
Valid only for battery-powered versions
544
Battery alarm limit
80
0 ... 90
R/W
Present an alarm when the consumed ener-
gy exceeds this percentage of the battery
capacity.
Valid only for battery-powered versions
** Maintenance = Read only
A.4
Meter setup
Table A- 4
Meter setup parameters
Parameter
Default
value
Value
range
Access
level
Description
Meter Setup
307
Flow velocity offset
0 m/s
-10 ... 10
m/s
HW key
Velocity added to measured flow velocity
310
Calibration factor
1.0
0 ... 2
R/W
This calibration factor will be calculated at
the factory with wet-calibration.
311
Adjustment Factor
1
- 2 ... 2
R/W
Meter correction factor for customer ad-
justment of the calculated flow value. Can
be used at installations where a reference
meter is used to get reference to the true
flow rate
312
Transducer cable length
Product
dependent
0 ... 200 m R/W
Cable length (m) from sensor to transmitter
372
Filter time constant
Product
dependent
0 ... 100 s R/W
General time filter for flow measurement.
Filter constant is the time that must pass
before the filter's output value is at 70% of
the change of its input value. Higher num-
ber gives a slower and more stable flow
signal.
380
Protect linearization from
user access.
No
No, Yes
Read
Protection of the linearization parameters. It
is decided by the order number and cannot
be changed.
The linearization parameters are listed in
the device menu "Linearization"
Содержание SONO 3500 CT
Страница 1: ...Ultrasonic Flowmeter Operating Instructions SONO 3500 CT 07 2019 Edition ...
Страница 2: ......
Страница 8: ...Table of contents 6 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 14: ...Introduction 1 5 Further Information 12 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 38: ...Electrical connection 5 5 Sealing of SONO 3500 CT 36 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 50: ...Commissioning 6 4 Commissioning via PDM 48 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 54: ...Functions 7 4 Hardware key 52 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 64: ...Service and maintenance 8 7 Battery disposal 62 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...