AB243586442172en-001401
Electrical data, connections and wiring
The terminal box is provided with 2 triple
knockouts and 1 single knockout for power
supply and 4 double knockouts for the safety
control circuit.
The 3 power supply knockouts accommodate the
following diameters:
• Ø 50.8 mm (UL 1"1/2 conduit) and Ø 43.7
mm (UL 1"1/4 conduit) and Ø 34.5 mm (UL 1"
conduit)
• Ø 40.5 mm (ISO40) and Ø 32.2 mm (ISO32) and
Ø 25.5 mm (ISO25)
• Ø 25.5 mm (ISO25)
The 4 others knockouts are as follows:
• Ø 22.5 mm (PG16) (UL 1/2") and Ø 16.5 mm
(ISO16) (x2)
• 20.7 mm (ISO20 or PG13.5) (x2)
SH180-240-295-380*-485*
Except code 3
SH380 code 3
Power supply
Power supply
Black
Sump heater
Cover holding screws (x3)
Blue Brown
M1, M2
Control circuit
Terminal box
The motor protection module comes preinstalled
within the terminal box. Phase sequence
protection connections and thermistor
connections are pre-wired and should not be not
be removed. The module must be connected to
a power supply of the appropriate voltage. The
module terminals are 6.3-mm size Faston type.
L N S1 S2 M1 M2
L1 L2 L3
Black Blue Brown
Phase sequence input
Internal control contact
Safety
circuit
Thermistor
connection
Module power
IP rating
The compressor terminal box according to IEC529 is IP54 for all models when correctly sized IP54 rated
cable glands are used.
First numeral, level of protection against contact and foreign objects
5
- Dust protected
Second numeral, level of protection against water
4
- Protection against water splashing
Black
Blue
Brown
Faston 1/4" tabs
Power supply
Sump heater
Module
power supply
M1-M2
Control circuit
The terminal box is provided with Ø 50.5 mm
(ISO50) (UL 1"1/2 conduit) hole with possible
Ø 63.5 mm (ISO63) (UL 2" conduit) knockout for
power supply and 2 x Ø 22.5 mm (PG16)
(UL 1/2" conduit) knockouts for safety control
circuit.
The temperature inside the terminal box may not
exceed 70°C. Consequently, if the compressor is
installed in an enclosure, precautions must be
taken to avoid that the temperature around the
compressor and in the terminal box would rise
too much. The installation of ventilation on the
enclosure panels may be necessary. If not, the
electronic protection module may not operate
properly. Any compressor damage related to this
will not be covered by Danfoss warranty. In the
same manner, cables must be selected in a way
to insure that terminal box temperature does not
exceed 70°C.
Terminal box temperature
Application Guidelines