© Danfoss | August 2018
AQ00000211 |
39
ENGINEERING TOMORROW
This check ensures that the cut-off valve can achieve the blocked state, when the cut-off solenoid valve is de-energized.
By moving the EH-valve main spool in the mechanical deadband, it is ensured that no oil flow is send to the steering
Important
Electro-hydraulic steering (Auto-guidance, Fast-steering and AUX-steering) will not be enabled before the PVED-CLS
has passed this test.
Warning
By setting P3078
:
Cut-off valve monitoring POST timeout to 0 (Bypass off-road safety check), the Cut-off valve
diagnostics are disabled
.
Important
•
In most cases this test will be completed within 1 second, but if the oil has a very high viscosity, the time for
completing this test will increase; hence Danfoss recommends a relatively high value for P3078 to ensure the
PVED-CLS does not goes into fail safe mode in cold conditions.
•
If PVED-CLS is commanded to go to off-road mode before pump pressure is available, PVED-CLS will not be
able to perform this self-test and hence fail after the specified timeout set by P3078.
Name
A
ddr
es
s
D
at
a t
yp
e
U
ni
t
Description of parameter
U
se
r
Range
D
a
nf
o
ss
de
fa
ul
t
val
u
e
S
a
fet
y
cri
ti
ca
l
p
a
ra
m
et
ers
‘
S
’
Mi
n
.
M
ax.
Cut-off valve
monitoring POST
timeout
P3078
U16
x10mSec
Cut Off Valve Activation Timeout for COV Monitoring feature while
entering Off Road state.
INFO: Setting this parameter to 0 will bypass off-road safety check
OEM
0
1000
900
S
Table 9
7.1.2.2 Cut-off valve monitoring for EHi-H
This safety check will be executed if
P3081: Valve type
is set to 2
(EHi-H)
and a mode change from on-road mode to
off-road mode is requested. The cut off valve monitoring for EHi-H consists of IMD safety checks.
The PVED-CLS will set the EH-valve main spool set-point to a positive value inside the hydraulic deadband and
alternately turn the cut-off solenoid valve on and off. Each time the COV solenoid valve is toggled, the time is measured
from it is toggled until the EH-valve main spool has been observed moving. The measured time is then evaluated against
the value of
P3098: Safety-checks IMD – Rise time limits
and
P3099: Safety-checks IMD – Fall time limit
, for the rise
time (cut-off solenoid valve turned on) and the fall time (cut-off solenoid valve turned off) respectively. Once the
consecutive number of test passed, both rise times and fall times, is equal to the value of
P3100: Safety-checks IMD –
Pass criteria
, the test is evaluated as passed and it will be repeated with a negative EH-valve main spool set-point. Once
this test has passed as well, the PVED-CLS will be allowed to go into off-road mode.
Содержание PVED-CLS
Страница 6: ...6 Danfoss August 2018 AQ00000211 ENGINEERING TOMORROW ...
Страница 71: ... Danfoss August 2018 AQ00000211 71 ENGINEERING TOMORROW Figure 29 ...
Страница 127: ... Danfoss August 2018 AQ00000211 127 ENGINEERING TOMORROW ...
Страница 147: ... Danfoss August 2018 AQ00000211 147 ENGINEERING TOMORROW ...
Страница 182: ...182 Danfoss August 2018 AQ00000211 ENGINEERING TOMORROW ...