7.6 Quick Transfer of Parameter Settings
between Multiple Frequency Converters
Once the set-up of a frequency converter is complete,
Danfoss recommends that you store the data in the LCP or
on a PC via MCT 10 Set-up Software tool.
Data storage in LCP.
1.
Go to
0-50 LCP Copy
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
WARNING
Stop the motor before performing this operation.
You can now connect the LCP to another frequency
converter and copy the parameter settings to this
frequency converter as well.
Data transfer from LCP to frequency converter:
1.
Go to
0-50 LCP Copy
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
NOTE
Stop the motor before performing this operation.
7.7 Read-out and Programming of Indexed
Parameters
Use
7.4.3 QM2 - 3-10 - Preset Reference
as an example.
Choose the parameter, press [OK], and use the up/down
navigation keys to scroll through the indexed values. To
change the parameter value, select the indexed value and
press [OK]. Change the value by using the up/down keys.
Press [OK] to accept the new setting. Press [CANCEL] to
abort. Press [Back] to leave the parameter.
7.8 Initialise the Frequency Converter to
Default Settings in two Ways
7.8.1 Initialise the Frequency Converter to
Default Settings in two Ways
Recommended initialisation (via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
.
2.
Press [OK].
3.
Select
Initialisation
and Press [OK].
4.
Cut off the mains supply and wait until the
display turns off.
5.
Reconnect the mains supply - the frequency
converter is now reset.
Except the following
parameters.
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-33 Parity / Stop Bits
8-35 Minimum Response Delay
8-36 Maximum Response Delay
15-00 Operating Hours
to
15-05 Over Volt's
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-30 Alarm Log: Error Code
15-4* Drive identification parameters
Two finger initialization:
1.
Power off the frequency converter.
2.
Press [OK] and [MENU].
3.
Power up the frequency converter while still
pressing the keys above for 10 sec.
4.
The frequency converter is now reset, except the
following parameters:
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-4* Drive identification parameters
Initialisation of parameters is confirmed by AL80 in the
display after the power cycle.
Programming
VLT Micro Drive Design Guide
68
MG02K102 - VLT
®
is a registered Danfoss trademark
7
7