Instructions
48 | AN405821998738en-000102 - 118A5495A
© Danfoss | Climate Solutions | 2023.02 | LCA012A024
Annex A - Technical data
Nameplate
A
: Model
B
: Code number
C
: Application, Protection
D
: Refrigerant
E
: Housing Service Pressure (Maximum working pressure)
F
: Supply voltage, Rated Load Ampere, Maximum Continuous Current
G
: Serial Number and bar code
Danfoss
IP24
PS
HP
PS
LP/MP
PT
HP
PT
LP/MP
PED Category
Ⅱ
Voltage
TS
-20 / 43
℃
RLA
Danfoss Ltd., 22Wycombe End, HP9 1NB, GB
Danfoss A/S, 6430 Nordborg, Denmark
A
B
C
D
E
F
G
Condensing unit installation place (Service space)
Single unit installation
(*) A service space of 800mm minimum is
necessary if installed in series. More than 800
mm is nice to have to inspect or replace parts of
the condensing unit.
Take care not to interfere with the service space
during piping work. Where the necessary space
is not available, install a stand to run the piping
under the unit.
(*1) Be sure to keep more than 100mm spaces
when the unit contacts with a wall. If the unit
installed in succession, 10mm spaces is enough.
(*2) A space of 330mm is necessary when the
power cable is taken in from L2 side, where
units are installed in series.
28 X 14
1350
1000
500
764
764
1691.5
261.6
264.4
740
Z
≥ L1
≥ L2
≥ L3
≥ L4
800
500
X
Z
X
28 X 14
19
726
F
F
F
F
425
425
250
250
850
19
Wall height ≤ H4
Wall height ≤ H3
Service space
Service space
Wall height
≤ H2
Installation
Example
I
II
L1
800
800
L2
10
10
L3
800
800
L4
100(*)
500
H1
1500
1500
H2
Not limited Not limited
H3
1000
1000
H4
Not limited Not limited