AQ251486498741en-010501 | 1
© Danfoss | 2020.10
NovoCon® S
- High Accuracy Actuator
Operating Guide
❶
IP40
IP54
IP5
4
IP5
4
❸
❺
①
②
❼
NovoCon® analog cable
❻
Manuel Calibration:
Press button
①
until two LED’s are turned on, and
then release again.
DIP switch:
②
Manual override: Adjust wheel
③
③
②
①
Common ground shall be
used for all devices on the
same network.
Digital port
Port for CO6 actuator or Energy cable, I/O cable,
analog cable or voltage booster.
Digital port
❷
❹
Actuator NovoCon® ChangeOver
6
Flexible
Cable NovoCon®
Temperature I/O
Red
Power 24V (in/out)
Black
Power ground (in/out)
Blue
Ground T1, T2, V/mA input & V output signal
Grey
V/mA input signal
White
V output signal
T1
T2
NovoCon® Energy cable
- PT1000 surface sensors
NovoCon® Energy cable
- PT1000 immersed sensors
Red
Power 24V
Black GND
Grey
Analog input
Blue
Analog input ground
NovoCon® digital cable
Red Power
Black
Green
´+´ non-inverting signal wire
White/green ´−´ inverting signal wire
Common ground for power
and bus signal wire
Purple O-ring
Actuator NovoCon®
ChangeOver
6
Red
Power 24V
Black GND
White
CO6 Control signal
Grey
CO6 Feedback signal
Blue O-ring
Actuator NovoCon®
ChangeOver
6
Energy
NovoCon®
I/O cable
Red
Power 24V
Black
Power ground
Blue
Ground T1, T2, V/mA input & V output signal
Grey
V/mA input signal
White
V output signal
Yellow
T1 or resistance input
Orange T2 or resistance input