6 Parameters
6.1 Parameter Overview
6.1.1 Parameter List
Parameter
Default value
Range
Conversion
index
Data
type
Dig. and ctrl. word [0]
[0 - 2]
-
5
8-02 Control Source
Option A
[0 - 4]
-
5
8-03 Control Timeout Time
1 s
0.1 - 18000
- 1
7
Off [0]
[0 - 10]
-
5
Hold set-up [0]
[0 - 1]
-
5
Do not reset [0]
[0 - 1]
-
5
Disable [0]
[0 - 3]
-
5
8-10 Control Profile
FC [0]
[0 - x]
-
5
8-30 Protocol
FC
8-31 Address
1
[0 – 255]
8-32 Baud Rate
9600
[0 – 7]
No Parity, 1 Stop Bit
10mS
5000mS
25.00mS
Logic OR [3]
[0 - 3]
-
5
Logic OR [3]
[0 - 3]
-
5
Logic OR [3]
[0 - 3]
-
5
Logic OR [3]
[0 - 3]
-
5
Logic OR [3]
[0 - 3]
-
5
Logic OR [3]
[0 - 3]
-
5
8-70 BACnet Device Instance
1
[1-4194304]
-
8-72 MS/TP Max Masters
127
[1-127]
-
8-73 MS/TP Max Info Frames
8-74 "I-Am" Service
Once at powerup [0]
[0-1]
-
8-75 Initialisation Password
“admin”
String[19]
Table 6.1 BACnet Specific Parameter List
Please refer to the
VLT
®
HVAC Drive Drive Operating Instructions, MG.11.Ax.yy
for a comprehensive parameter list or to the
VLT
®
HVAC Drive Drive Programming Guide, MG.11.Cx.yy
for detailed descriptions of parameters.
Conversion index
This number refers to a conversion figure used when writing or reading to and from the frequency converter.
Conv.
index
100
67
6
5
4
3
2
1
0
-1
-2
-3
-4
-5
-6
Conv.
factor
1
1/60
1000000
100000
10000
1000
100
10
1
0.1
0.01
0.001
0.0001
0.00001
0.000001
Parameters
VLT
®
HVAC Drive Native BACnet Operating Instructions
22
MG.14.C1.02 - VLT
®
is a registered Danfoss trademark