1
FRCC.EI.002.A1.02 © Danfoss Commercial Compressors 04/08
The compressor must only be
used for its designed purpose(s) and
within its scope of application (refer
to «operating limits»).
Consult Application guidelines and da-
tasheet available from cc.danfoss.com
The compressor is delivered under
nitrogen gas pressure (between 0.3
and 0.7 bar) and hence cannot be
connected as is; refer to the «as-
sembly»
section for further details.
Under all circumstances, the
EN378 (or other applicable local safety
regulation) requirements must be
fulfilled.
The compressor must be handled
with caution in the vertical posi-
tion (maximum offset from the
vertical : 15°)
Operating limits
MT
MTZ
MTZ
MTZ
NTZ
R22
R407C
R134a
R404A / R507A
High side pressure range
bar (g)
10,9 - 27,7
12,5 - 29,4
7,9 - 22,6
13,2 - 27,7
13,2 - 27,7
Low side pressure range
bar (g)
1,0 - 7,0
1,4 - 6,6
0,6 - 4,7
1,0 - 7,2
0,1 - 3,3
Discharge temperature must be kept lower than 130°C
Housing
Service
Pressure
Lubricant
Supply Voltage
Maximum current
Starting current
Model
Number
Serial
Number
1" : 80 Nm
1"1/4 : 90 Nm
1"3/4 : 110 Nm
Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering
practice relating to installation, commissioning, maintenance and service.
HM8-40
15 Nm
230 V
A + C
Thermostat
C
S
R
IOL
1
PSC
1
CSR
3
230 V
Thermostat
BµF
Start Relay
5
2
1
15 kΩ -1 w
C
S
R
IOL
A + C
C
R
S
C
R
S
Never operate compressors without terminal cover fitted
15 Nm
HM12-50
∼
∼
∼
INSTRuCTIONS
MT / MTZ / NTZ COMPReSSORS