Parame‐
ter
Options/
valid
range
De‐
fault
value
Description
Con‐
ver‐
sion
index
Data
type
42-61 Des-
tination
Address
1–65535
1
Enter the safe fieldbus destination address within the safe network.
This address must be unique in the network where PROFIsafe oper-
ates. The address should match the address specified in the PLC soft-
ware.
–
u_int16
7.2.4 Parameter Group 42-8* Status
Table 12: 42-8* Status
Parameter
Options/valid
range
Default
value
Description
Con‐
ver‐
sion
index
Data
type
42-80 Safe Op-
tion Status
0 - 0xFFFFFFFF
0
Shows the status word of the VLT® Safety Option MCB 152
as a hexadecimal value. For more information, see
0
u_int32
42-81 Safe Op-
tion Status 2
0 - 0x7FFFFFFF
0
Shows the status 2 word of the VLT® Safety Option MCB
152 as a hexadecimal value. For more information, see
.
0
u_int32
42-82 Safe
Control Word
0 - 0xFFFFFFFF
0
Shows the safe control word as a hexadecimal value.
–
u_int32
42-83 Safe
Status Word
0 - 0xFFFFFFFF
0
Shows the safe status word as a hexadecimal value.
–
u_int32
42-85 Active
Safe Func.
[0] STO
[10] None
[10]
None
Shows the currently active safety function. Use
parameter
0-20 Display Line 1.1 Small
to
parameter 0-22 Display Line 1.3
Small
to show the function on the LCP.
–
u_int8
42-86 Safe Op-
tion Info
Safe Option
Messages,
String Length 25
0
Shows information about the safety option. The LCP can
show this parameter in the large display line. Can be selec-
ted in
parameter 0-23 Display Line 2 Large
and
parameter
0-24 Display Line 3 Large
.
0
Visible-
String
42-87 Time
Until Manual
Test
0–8761 h
8761 h
Shows the remaining time in hours until yearly test has to
be performed.
•
[0] indicates PUST warning.
•
[1] indicates speed suspension warning (Not used for
MCB 152).
•
[2] indicates DI1 offline test required.
•
[3] indicates DI2 offline test required.
0
u_int16
Parameter Setup
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578| 51
Danfoss A/S © 2020.02