Instructions
1.
Remove LCP panel from the frequency converter.
2.
Remove the frame located beneath and discard it.
3.
Push the option into place. The Ethernet
connectors must be facing upwards.
4.
Remove both knock-outs on the fieldbus option
adapter frame.
5.
Push the fieldbus option adapter frame for the
frequency converter into place.
6.
Replace the LCP and attach cable.
NOTICE
Do not strip the Ethernet cable and ground it via the strain
relief-plate! The grounding of screened Ethernet cable is
done through the RJ-45 connector on the option.
NOTICE
After installing the MCA 122 option, be aware of the
following parameter settings:
8-01 Control Site
:
[2] control word only
or
[0] Digital and ctrl.
[3] Option A
2.1.2 LED Behaviour
The option has three bi-coloured LEDs
LED label
Description
MS
Module Status
NS1
Network Status Ethernet Port 1
NS2
Network Status Ethernet Port 2
Table 2.1 Description of LEDs
State
LED
Description
No power
Off
The device is un-powered
Device operational
Green:
Solid green
The device is operational
Standby
Green:
Flashing green
The device needs commissioning
Minor fault
Red:
Flashing red
The device has detected a recoverable fault
Major fault
Red:
Solid red
The device has detected an un-recoverable
fault
Self test
Red:
Flashing red/
green
The Modbus TCP option is in self-test mode
Green:
No IP address
Yellow
Steady yellow
No IP address configured or obtained
Wink
Yellow
Flashing yellow
Flash for 20 s
Table 2.2 MS: Module Status
State
LED
Description
No IP-address (no
power)
Off
No link present (or is un-powered)
Connected
Green:
Solid green
Link present; but nor winked and no ACD
Duplicate IP
Red:
Solid red
The IP-address assigned to the device is
already in use
Self test
Red:
Flashing red/
green
The Modbus TCP is in self-test mode
Green
Device has been winked Yellow
Flashing yellow
Flash for 20 s
Link present at 10 Mbps Yellow
Steady yellow
Link present; but nor winked and no ACD
Table 2.3 NS1+NS2: Network Status (One per Port)
How to Install
MCA 122 Modbus TCP
6
MG90P202 - VLT
®
is a protected Danfoss trademark