20 DKDHR
VI.GP.B1.02
Danfoss District Energy
Instructions
Kompakt H 28/35/42
14.0 Domestic hot water
14.1 Domestic hot water temperature control
Factory-setting of the controller is 50°C for the domestic hot water
temperature. In periods with higher demands the controller set-
tings can be changed in accordance with the enclosed producer
instructions.
Installation & Maintenance
ECL Comfort 300/C66
14.2 2-vay valve + actuator
The ECL 300 variants are supplied with an 2-way valve VS2 or VM2
and an electronic actuator AM10 or 150, which in combination
with the ECL controller controls the DHW circuit.
The electrical actuator has undergone a functional test from fac-
tory. In case of operating disturbances the actuator can be closed
manually.
Close the actuator by turning the manual override knob on top of
actuator counter-clockwise.
Please see enclosed instructions,
Electrical actuator AMV
2-vay valve
The H 28/35/42 substations are supplied with connection pipes
for domestic hot water cylinder on the primary side.
The substations H 228/235/242 with ECL 200 include no control
equipment for the domestic hot water cylinder.
The substations H 328/335/342 with ECL 300 are supplied with a
2-way valve and an actuator, which in combination with the ECL
300 controller controls the domestic hot water temperature in the
cylinder.
Further more an immersion sensor for installation in a sensor poc-
ket in the cylinder is supplied separately for the H 328/335/342
with ECL 300.
For further information please see page 12.
H 335 / H 342
Actuator AMV 10
Tab
le
of C
ont
ent
s
Dai
ly
use
Sec
tio
n
1
Cho
ose
fa
vou
rite
d
isp
lay
2
Sel
ect
co
ntro
lle
r m
ode
3
Adjust room
and hot
water temperature
4
Set personal
day plan
5
Advantages of
the ECL
Card
6
Hot points
7
Def
ini
tio
ns
The
do
cum
ent
atio
n fo
r th
e E
CL
Com
for
t c
ont
rol
ler
is
com
pos
ed
of n
um
ber
ed
sec
tio
ns.
O
nly
se
ctio
ns
tha
t a
re
rel
eva
nt t
o y
our
E
CL
Com
for
t c
ont
rol
ler
ar
e in
clu
ded
he
re.
Your
personal week
plan:
Hea
tin
g
0
3
6
9
12
15
18
21
24
1
Mon
day
2
Tue
sda
y
3
Wed
nes
day
4
Thu
rsd
ay
5
Frid
ay
6
Sat
urd
ay
7
Sun
day
Hot
W
ate
r
0
3
6
9
12
15
18
21
24
1
Mon
day
2
Tue
sda
y
3
Wed
nes
day
4
Thu
rsd
ay
5
Frid
ay
6
Sat
urd
ay
7
Sun
day
Fac
tor
y se
ttin
gs a
re
gre
y.
8
23
-
5 -
8
18
- 2
2
6-8
16
-
2
2
Installation and
maintenance.
Grey
sections 10
and
onwards. Turn
the guide
over.
This guide
is associated
to ECL
Card 087B4757
Ins
tal
ler
:
By:
Dat
e:
Table of Contents
Sections of the Installer’s part of this guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections relevant to
your ECL Comfort controller are included here.
Before you start
Installation
10
Identifying the system type
11
Mounting the ECL Comfort controller
12
Electrical connections 230 V a.c.
13
Electrical connections 24 V a.c.
14
Placing the temperature sensors
15
Inserting the ECL Card
Basic Set-up
16
Adjusting the ECL Card settings
17
Setting the time and date - Line A
18
Monitoring temperatures and system units - Line B
19
Manual control - Line B
20
Setting the heat curve - Line C
21
Heating cut-out - Line 1
22
Flow temperature limits - Line 2
23
Room temperature influence - Line 3
26
Setting PI-regulation - Line 4 - 7
27
Hot water controller - line 1 and 2
Control & Overviews
29
Check list
30
ECL Card settings
31
Service parameters
Extended Service
32
Adjusting the service parameters
Miscellaneous
34
Copying with the ECL Card
Daily use,
turn the guide over sections 01 - 07
1
Choose favourite display
2
Select controller mode
3
Adjust room and hot water temperature
4
Set personal day plan
5
Advantages of the ECL Card
6
Hot points
7
Definitions
8
23
-
ECL COMFORT
ECL Comfort
Installation and
Maintenance
Mixing controller with PI-controlled
hot water service
C66
V
I.7
C
.C
4.
02
ECL COMFORT
EC
L C
om
for
t
U
ser
’s
Gui
de
C66
H 328
2-vay valve
Actuator AMV 150
7369267-9 SIBC R&D
EI.97.Q2.00 © Danfoss 12/01
1
INSTRUCTIONS
VS2 2-way
06
5R
90
75
06
5R
90
75
DN
L (mm)
15
65
20
70
25
75
DN
L
1
(mm)
15
131
20
142
25
159
DN
L
2
(mm)
15
139
20
154
25
159
DN
L
3
(mm)
15
69
20
74
25
79
7369053-0 SIBC
VI.HB.C1.00 © Danfoss 5/02
1
Instructions
VM2, VB2 2-way
06
5R
90
74
06
5R
90
74
DN
L (mm)
15
65
20
70
25
75
32
100
40
110
50
130
DN
L
1
(mm)
15
131
20
142
25
159
32
196
40
196
50
228
DN
L
2
(mm)
15
139
20
154
25
159
32
184
40
294
50
330
DN
L
3
(mm)
15
69
20
74
25
79
32
104
40
114
50
134
VM2
VB2
1
Installation Guide
AMV 10
Danfoss Heating
EI.96.E3.00
DH-SMT/SI
❶
❷
❸
N-1
N-3
AMV 10 +
AMV 10 +
AMV 10 +
AMV 10 +
VM 2 (DN 15-25), VS 2
VB 2 (DN 15-20)
VMV
AVQM (DN 15-20)
Instructions
AMV 150
73691180 DH-SMT/SI
VI.KU.N2.1J © Danfoss 01/2008
1
ENglIsh
Actuators for three point control AMV 150
www.danfoss.com
Page 2
DANsK
Motorer til 3-punkts styring AMV 150
www.danfoss.dk
Side 3
DEUTsCh
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150
www.danfoss.de
Seite 3
sVENsKA
Motor för 3-punktsreglering AMV 150
varme.danfoss.se
Sida 4
NEDERlANDs
Servomotor met 3-puntssturing AMV 150
www.danfoss.nl
Pagina 4
lIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150
www.danfoss.lt
5 puslapis
lATVIsKI
Motori trīs punktu kontrolei AMV 150
www.danfoss.com
Lpp. 5
MAgYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150
www.danfoss.com
6. oldal
ČEsKY
Servopohony s tříbodovým regulačním signálem AMV 150
www.danfoss.cz
Strana 6
POlsKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150
www.danfoss.pl
Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru
Страница 7
AMV 150 +
AMV 150 +
AMV 150 +
VS2 (DN 15)
VMV
AVQM (DN 15)