Troubleshooting

Find out how to ensure the outputs of the I/O module function properly, and make sure your changes to

parameters are saved.

Problem

Cause

Solution

Outputs of I/O module do not
function as expected. Configured is
always false.

The I/O module is using variable address mode
and the CAN shield voltage does not fall within
the range matching the function block’s N1
value.

Use the 

I/O Module CAN Message Identifiers

 table to find the

correct voltage and ensure it is applied to the CAN shield
during power up.

Change the N1 value in the function block to match the
voltage applied to the CAN shield.

Incompat_HW is true. The function block is
communicating with a device other than the I/O
module.

Ensure the proper addressing mode and corresponding
communication parameters are set on both the I/O module
and the function block.

It is possible the I/O module is correctly configured, but a
second I/O module has a similar configuration. Review
configuration and make changes to the other I/O modules.

Incompat_Protocl is true. The firmware on the
I/O module uses a version of the I/O Protocol less
than 2.00.

Update the I/O module with the latest firmware.

Incompat_Protocl is true. The firmware on the
I/O module uses a version of the I/O Protocol
later than version 2.99.

Replace the function block by using the latest available
HWD file.

When changing the I/O module ’s
parameters with the 
PLUS+1

®

 Service

Tool, those changes are not properly
saved.

A function block detects the changes and resets
the parameters to the values specified in the
function block.

Disconnect the function block’s controller before making
parameter changes. If the changes do not result in different
CAN message identifiers for the I/O module, then
reconnecting the controller results in the parameters
reverting back to the values set in the function block.

User Manual

PLUS+1® Compliant IX012-010 Function Block

IX012-010 Function Block

 

©

 Danfoss | July 2018

11063398 | AQ00000107en-US0101 | 11

Содержание IX012-010

Страница 1: ...User Manual PLUS 1 Compliant IX012 010 Function Block www danfoss com...

Страница 2: ...Revision history Table of revisions Date Changed Rev July 2018 Rebranding 0101 June 2009 AA User Manual PLUS 1 Compliant IX012 010 Function Block 2 Danfoss July 2018 11063398 AQ00000107en US0101...

Страница 3: ...s and Signal Overview 8 Configuring Communications 9 Variable Addressing Mode 9 Predefined Addressing Mode 9 Fixed Addressing Mode 9 Volatile Parameters 9 Non Volatile Parameters 10 Timing Configurati...

Страница 4: ...e The CAN messages use 11 bit identifiers in this mode 2 Fixed ID addressing mode The I O module Tx and Rx message identifiers are determined directly by setting Tx ID and Rx ID The CAN messages use e...

Страница 5: ...ines how often the Power Sensor Power and CAN Shield input values are transmitted from the I O module 1000 is 1 ms RepTime_DigAn_In U16 0 65535 Determines how often the DigIn and AnIn values are trans...

Страница 6: ...h Supply Voltage The internal Pull Up resistor is connected to an internal 5 V The internal Pull Down resistor is connected to Ground PinConfig1 U16 Output 0 3 Sets the maximum input voltage to allow...

Страница 7: ...ear in both the Input and Output buses Signal Type Direction Range Description CAN Bus CommStatus U16 Input 1 8 255 Current status of communication with the I O module 0 CAN message transmission is di...

Страница 8: ...on block requires I O module hardware using protocol version 2 00 to 2 99 ProtocolVersion U16 Input 0 65535 I O communication protocol version used by the I O module hardware 200 is version 2 00 Conne...

Страница 9: ...module In this mode the I O module reads the N1 value stored in non volatile memory EEPROM Because the function block and the I O module use different default addressing modes as long as the N1 value...

Страница 10: ...ion on a CAN bus Use the PLUS 1 CG150 USB CAN gateway and CANKing software to view CAN bus loads PLUS 1 I O modules communicate with their associated controllers over a CAN bus System developers can a...

Страница 11: ...nfigured but a second I O module has a similar configuration Review configuration and make changes to the other I O modules Incompat_Protocl is true The firmware on the I O module uses a version of th...

Страница 12: ...lutions ApS Nordborgvej 81 DK 6430 Nordborg Denmark Phone 45 7488 2222 Danfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading S...

Отзывы: