11 Specifications
11.1 General Specifications
Mains supply (L1, L2, L3)
Supply voltage
380-480 V
±
10%
Supply voltage
525-600 V
±
10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
maximum once/2 min.
Environment according to EN60664-1
overvoltage category III / pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage
0-100% of supply voltage
Output frequency
0-800* Hz
Switching on output
Unlimited
Ramp times
1-3600 s
* Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
maximum 110% for 1 min.
*
Starting torque
maximum 135% up to 0.5 s
*
Overload torque (Constant torque)
maximum 110% for 1 min.
*
*Percentage relates to the frequency converter's nominal torque.
Cable lengths and cross sections
Max. motor cable length, screened/armoured
150 m
Max. motor cable length, unscreened/unarmoured
300 m
Max. cross section to motor, mains, load sharing and brake *
Maximum cross section to control terminals, rigid wire
1.5 mm
2
/16 AWG (2x0.75 mm
2
)
Maximum cross section to control terminals, flexible cable
1 mm
2
/18 AWG
Maximum cross section to control terminals, cable with enclosed core
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
* See 11.2.1 Mains Supply 3x380-480 VAC - High Power for more information!
Specifications
VLT® Refrigeration Drive 110-250 kW Operating Instructions
MG16F102 - VLT® is a registered Danfoss trademark
63
11
11