FC 300 Instruction Manual
Safety Instructions and General Warning
"
High voltage warning
The voltage of the FC 300 is dangerous whenever the converter is connected to electrical
power. Incorrect fitting of the motor or adjustable frequency drive may cause damage to
the equipment, serious injury or death. Consequently, it is essential to comply with the
instructions in this manual as well as local and national rules and safety regulations.
"
Safety Instructions
•
Make sure the FC 300 is properly connected to ground.
•
Do not remove mains plugs or motor plugs while the FC 300 is connected to mains.
•
Protect users against supply voltage.
•
Protect the motor against overloading according to national and local regulations.
•
Motor overload protection is not included in the default settings. To add this function, set parameter
1-90
Motor thermal protection
to value
ETR trip
or
ETR warning
. For the North American market:
ETR functions provide class 20 motor overload protection, in accordance with NEC.
•
The ground leakage current exceeds 3.5 mA.
•
The [OFF] key is not a safety switch. It does not disconnect the FC 300 from mains.
"
Before Commencing Repair Work
1.
Disconnect FC 300 from AC line.
2.
Disconnect DC bus terminals 88 and 89
3.
Wait at least 4 minutes
4.
Remove motor plugs
"
High start torque
While FC 300 is connected to AC line, the motor can be started/stopped using digital
commands, bus commands, references or a local stop.
•
Disconnect the FC 300 from AC line whenever personal safety considerations make
it necessary to avoid unintended start.
•
To avoid unintended start, always activate the [OFF] key before changing parameters.
•
Unless terminal 37 is turned off, an electronic fault, temporary overload, a fault in the AC line
supply, or lost motor connection may cause a stopped motor to start.
"
Safe Stop of FC 302
The FC 302 can perform the Designated Safety Function
Uncontrolled Stopping
by removal of power. (as
defined by draft IEC 61800-5-2) or
Stop Category 0
(as defined in EN 60204-1). It is designed and approved
suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe Stop.
In order to install and use the Safe Stop function in accordance with the requirements of Safety
Category 3 in EN 954-1, the related information and instructions of the FC 300 Design Guide
MG.33.BX.YY must be followed! The information and instructions of the Instruction Manual are
not sufficient for a correct and safe use of the Safe Stop functionality!
8
MG.33.A4.22 - VLT is a registered Danfoss trademark
Содержание FC 302
Страница 34: ...FC 300 Instruction Manual How to Install 34 MG 33 A4 22 VLT is a registered Danfoss trademark...
Страница 74: ...FC 300 Instruction Manual Troubleshooting 74 MG 33 A4 22 VLT is a registered Danfoss trademark...