FC 300 Instruction Manual
How to Install
"
Final Set-Up and Test
To test the set-up and ensure that the adjustable frequency drive is running, follow these steps.
Step 1. Locate the motor nameplate.
NOTE
The motor is either star- (Y) or delta-
connected (
∆
). This information is located
on the motor nameplate data.
Step 2. Enter the motor nameplate data
in this parameter list.
To access this list, first press the [QUICK MENU]
key then select “Q2 Quick Setup”.
1.
Motor Power [kW]
or Motor Power [HP]
par. 1-20
par. 1-21
2.
Motor Voltage
par. 1-22
3.
Motor Frequency
par. 1-23
4.
Motor Current
par. 1-24
5.
Motor Nominal Speed
par. 1-25
Step 3. Activate the Automatic Motor Adaptation (AMA)
Performing an AMA will ensure optimum performance. The AMA measures the values
from the motor model equivalent diagram.
1.
Connect terminal 37 to terminal 12.
2.
Start the adjustable frequency drive and activate the AMA par. 1-29.
3.
Choose between complete or reduced AMA. If an LC filter is mounted, run only the reduced
AMA, or remove the LC filter during the AMA procedure.
4.
Press the [OK] key. The display shows “Press [Hand on] to start”.
5.
Press the [Hand on] key. A progress bar indicates if the AMA is in progress.
24
MG.33.A4.22 - VLT is a registered Danfoss trademark