FC 300 Instruction Manual
How to Install
IP 21/IP 4X/ TYPE 1 Enclosure Kit
The IP 21/IP 4X/ TYPE 1 enclosure kit consists
of a sheet metal part and a plastic part. The
sheet metal part serves as bonding plate for
conduits and is attached to the bottom of the
heat sink. The plastic part serves as protection
from live parts on power plugs.
Mechanical
dimensions
Frame
size A2
Frame
size A3
Height
A
14.8 in
(375 mm)
14.8 in
(375 mm)
Width
B
3.54 in
(90 mm)
5.12 in
(130 mm)
Bottom depth
from back plate
to front
C
7.95 in
(202 mm)
7.95 in
(202 mm)
Top depth from
back plate
to front (w/o
option)
D
8.15 in
(207 mm)
8.15 in
(207 mm)
Top depth from
back plate to
front (w/ option)
D
8.74 in
(222 mm)
8.74 in
(222 mm)
Mechanical dimensions of the IP 21/IP 4x/
TYPE 1 enclosure kit
1.
Drill holes in accordance with the measurements given.
2.
You must provide screws suitable for the surface on which you want to mount
the FC 300. Retighten all four screws.
FC 300 IP20 allows side-by-side installation. Because of the need for cooling, there must be a
minimum of 4 in (100 mm) free air passage above and below the FC 300.
14
MG.33.A4.22 - VLT is a registered Danfoss trademark