Introduction
Stepper Valve Driver EKF series is for use where stepper motor valves must be accurately controlled,
typically in commercial air conditioning, heat pumps, commercial refrigeration and food retailing
applications.
Supply voltage
EKF 1A: 24 V AC / DC 50 / 60 Hz
EKF 2A: 24 V AC / DC, 50 / 60 Hz
Power consumption
Idle operating: < 1 W (without valve)
Power consumption for using 1 valve.
CCMT 16 – CCMT 42: 25 VA / 15 W
ETS 5M, ETS 6: 20 VA / 10 W
ETS 12C – ETS 100C, KVS C: 30 VA /15 W
ETS 12.5 – 400: 10 VA / 5 W
ETS 500P, 800P: 28 VA / 20 W
CCMT 2- CCMT 8: 10 VA / 5 W
CTR 20: 14 VA / 10 W
CCMT L: 20 VA / 10 W
When using two valves sum the power consumption of each valve.
Analog inputs
EKF 1A: 1 input AI1
0-5 V, 0-10 V, 4-20 mA, 0-20 mA
EKF 2A: 2 inputs AI1 and AI2
0-5 V, 0-10 V, 4-20 mA, 0-20 mA
Max. 15 V Analog input voltage. Do not connect voltage sources to unpowered units
without limiting the current to analog inputs (overall 40 mA per input).
Input Impedance: >50 kΩ (Voltage Input) 120 Ω ± 2% (Current Input)
Digital outputs
1 output for EKF1A / EKF 2A: D01 (open collector), sink current max 10 mA
Valve support
EKF 1A: 1 stepper motor valve output, EKF 2A: 2 stepper motor valve output
STEPPER 1: A1, A2, B1, B2
STEPPER 2: A1, A2, B1, B2
Bipolar and unipolar stepper motor output:
- Danfoss ETS / KVS / ETS C / KVS C / CCMT 2 – CCMT 42 / CTR / CCMT L Valves
- ETS 6 / ETS 5M Valves
Open circuit HW diagnostics is present.
Battery backup
1 input for EKF 1A / EKF2A: Vbat
BAT, GND: Nominal 18 – 24 V DC, Min 16 V DC - Max 28 V DC (EKE 2U
recommended)
Max. battery current: 2 A at 18 V (valve depended)
Battery alarm/warning will be activated below 16 V DC.
Enviroment
Storage
-30 – 80 °C / -22 – 176 °F
Operating
-20 – 60 °C / -4 – 140 °F
Humidity
< 90% RH, non-condensing
DIN Mounting
4 DIN
Technical Specificatons