Manual

Superheat Controller, 

type EKD 316

Advantages

 

ƒ

The superheat is regulated to the lowest 

possible value. 

 

ƒ

The evaporator is charged optimally – even 

when there are great variations of load and 

suction pressure.

 

ƒ

Energy savings – the adaptive regulation of 

the refrigerant injection ensures optimum 

utilisation of the evaporator and thus a high 

suction pressure.

EKD 316 is a superheat controller for the 

stepper motor valve that can be used where 

there are requirements for accurate control of 

superheat in connection with refrigeration. 

The controller and valve can be used where 

there are  requirements for accurate control of 

superheat in connection with refrigeration.

Applications:

 

ƒ

Processing plant (water chillers)

 

ƒ

Cold store (air coolers)

 

ƒ

A/C plant

 

ƒ

Heat pumps

 

ƒ

Air conditioning

 

ƒ

Regulation of superheat

 

ƒ

MOP function

 

ƒ

ON/OFF input for start/stop of regulation

 

ƒ

Relay output to alarm

 

ƒ

MOD bus communication 

 

ƒ

Safety features and 

 

ƒ

Alarm indications

Main features

Содержание EKD 316

Страница 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Страница 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Страница 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Страница 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Страница 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Страница 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Страница 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Страница 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Страница 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Страница 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Страница 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Страница 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Отзывы: