MENU > Settings > Control parameters, circulation pump(s)
Xp (proportional band)
1x184
See Appendix “Parameter ID overview”
Set the proportional band. A higher value will result in a stable but
slow control of the flow temperature.
MENU > Settings > Control parameters, circulation pump(s)
Tn (integration time ) (A333.2 / A333.3)
12185
Circuit
Setting range
Factory setting
1
1 . . . 999 sec
5 sec
Set the integration time for the control of the pressure difference between
S9 and S10.
Low value:
Controller reacts fast, but with less stability
High value:
Controller reacts slow and with higher stability
MENU > Settings > Control parameters, circulation pump(s)
Nz (neutral zone) (A333.2 / A333.3)
12187
Circuit
Setting range
Factory setting
1
0.1 . . . 2.0 bar
1.0 bar
Set the acceptable pressure difference deviation.
When the actual pressure difference is within the neutral zone, the controller
does not change the circulation pump speed.
Low value:
A low variation in pressure is acceptable
High value:
A high variation in pressure is acceptable
The neutral zone is symmetrical around the desired pressure difference
value, i.e. half the value is above and half the value is below.
MENU > Settings > Control parameters, circulation pump(s)
Td (Time derivative) (A333.2 / A333.3)
12197
Circuit
Setting range
Factory setting
1
0 . . . 250 sec
0 sec
The Td related function can avoid a too aggressive reaction in the speed
control procedure.
0:
No influence
Low value:
Minor influence
High value:
Major influence