MENU > Settings > Control parameters, refill pump(s)
V out min. (A333.2 / A333.3)
13167
Circuit
Setting range
Factory setting
1
0 . . . 100 %
0 %
The output voltage for controlling the speed of the refill pump can be limited
to a minimum value.
See also "V out max".
0 - 100:
The value in % expresses the maximum voltage for
controlling the analogue output for the speed control
of the refill pump.
Example:
A setting of 15 % means that the output voltage will be 1.5 volt as a
minimum.
The setting of "V.out min" has priority over "V.out max".
MENU > Settings > Control parameters, refill pump(s)
Sleep level (A333.2 / A333.3)
11331
Circuit
Setting range
Factory setting
1
OFF / 1 . . . 100 %
20 %
When the speed control signal gets below the "Sleep level" value, the speed
will be set to 0 (zero) % after elapse of "Sleep mode time".
The refill pump stops (goes into sleep mode).
The set value is also the speed level at a new refill procedure.
This function protects the refill pump against low speed.
See also: "Sleep mode time" and "Wake up level".
OFF:
The sleep function is disabled
1 - 100:
The sleep function is enabled
X
= Time
Y
= Speed control signal (0 - 10 V) (%))
# 1 # = Actual control signal
# 2 # = Sleep level
# 3 # = Wake-up level
# 4 # = Sleep mode time
MENU > Settings > Control parameters, refill pump(s)
Sleep mode time (A333.2 / A333.3)
11332
Circuit
Setting range
Factory setting
1
0 . . . 300 sec
10 sec
The "Sleep mode time" determines a delayed stop of the refill pump at too
low speed.
See also: "Sleep level" and "Wake up level".
0 - 300:
Set the sleep mode time (in seconds)
VI.GU.T2.02
© Danfoss | 2017.09 | 95
Operating Guide ECL Comfort 310, application A333