MENU > Settings > Control parameters, refill pump(s)
Tn (integration time ) (A333.2 / A333.3)
13185
Circuit
Setting range
Factory setting
1
1 . . . 999 sec
25 sec
Set the integration time for the control of the pressure at S10.
Low value:
Controller reacts fast, but with less stability
High value:
Controller reacts slow and with higher stability
MENU > Settings > Control parameters, refill pump(s)
Nz (neutral zone) (A333.2 / A333.3)
13187
Circuit
Setting range
Factory setting
1
0.1 . . . 2.0 bar
0.4 bar
Set the acceptable pressure deviation at S10.
When the actual pressure is within the neutral zone, the controller does
not change the refill pump speed.
Low value:
A low variation in pressure is acceptable
High value:
A high variation in pressure is acceptable
The neutral zone is symmetrical around the desired pressure value, i.e.
half the value is above and half the value is below this pressure.
MENU > Settings > Control parameters, refill pump(s)
Td (Time derivative) (A333.2 / A333.3)
13197
Circuit
Setting range
Factory setting
1
0 . . . 250 sec
0 sec
The Td related function can avoid a too aggressive reaction in the speed
control procedure.
0:
No influence
Low value:
Minor influence
High value:
Major influence
MENU > Settings > Control parameters, refill pump(s)
V out max. (A333.2 / A333.3)
13165
Circuit
Setting range
Factory setting
1
0 . . . 100 %
100 %
The output voltage for controlling the speed of the refill pump can be limited
to a maximum value.
See also "V out min".
0 - 100:
The value in % expresses the maximum voltage
for controlling the analogue output for the speed
control of the refill pump.
Example:
A setting of 60 % means that the output voltage will be 6 volt as a
maximum.
The setting of "V.out min" has priority over "V.out max".