7.7 Parameter ID overview
A333.x —
x
refers to the subtypes listed in the column.
ID
Parameter Name
A333.x
Setting range
Factory
Unit
Own settings
11010
ECA addr.
2, 3
0 ... 0
0
11011
Auto saving
1, 2, 3
OFF, -29 ... 10
-15
°C
11012
Boost
1, 2, 3
OFF, 1 ... 99
OFF
%
11013
Ramp
1, 2, 3
OFF, 1 ... 99
OFF
Min
11014
Optimizer
1, 2, 3
OFF, 10 ... 59
OFF
11017
Demand offset
1, 2, 3
OFF, 1 ... 20
OFF
K
11021
Total stop
1, 2, 3
OFF ; ON
OFF
11022
P exercise
1, 2, 3
OFF, 1 ... 200
OFF
Sec
11023
M exercise
1, 2, 3
OFF ; ON
OFF
11026
Pre-stop
1, 2, 3
OFF ; ON
ON
11031
High T out X1
1, 2, 3
-60 ... 20
15
°C
11032
Low limit Y1
1, 2, 3
10 ... 150
40
°C
11033
Low T out X2
1, 2, 3
-60 ... 20
-15
°C
11034
High limit Y2
1, 2, 3
10 ... 150
60
°C
11035
Infl. - max.
1, 2, 3
-9.9 ... 9.9
0.0
11036
Infl. - min.
1, 2, 3
-9.9 ... 9.9
0.0
11037
Adapt. time
1, 2, 3
OFF, 1 ... 50
25
Sec
11052
DHW priority
1, 2, 3
OFF ; ON
OFF
11077
P frost T
1, 2, 3
OFF, -10 ... 20
2
°C
11078
P heat T
1, 2, 3
5 ... 40
20
°C
11085
Priority
1, 2, 3
OFF ; ON
OFF
11093
Frost pr. T
1, 2, 3
5 ... 40
10
°C
11109
Input type
1, 2, 3
EM1 ; EM2 ; EM3 ;
EM4 ; EM5 ; OFF
OFF
11112
Adapt. time
1, 2, 3
OFF, 1 ... 50
OFF
Sec
11113
Filter constant
1, 2, 3
1 ... 50
10
11115
Units
1, 2, 3
ml, l/h ; l, l/h ; ml,
m3/h ; l, m3/h ; Wh,
kW ; kWh, kW ; kWh,
MW ; MWh, MW ;
MWh, GW ; GWh,
GW
ml, l/h
11116
High limit Y2
1, 2, 3
0.0 ... 999.9
999.9
11117
Low limit Y1
1, 2, 3
0.0 ... 999.9
999.9
11118
Low T out X2
1, 2, 3
-60 ... 20
-15
°C
11119
High T out X1
1, 2, 3
-60 ... 20
15
°C
11141
Ext. input
1, 2, 3
OFF ; S1 ; S2 ; S3 ; S4
; S5 ; S6 ; S7 ; S8 ; S9 ;
S10 ; S11 ; S12 ; S13 ;
S14 ; S15 ; S16
OFF
11142
Ext. mode
1, 2, 3
COMFORT ; SAVING
COMFORT
11147
Upper difference
1, 2, 3
OFF, 1 ... 30
OFF
K
166 | © Danfoss | 2017.09
VI.GU.T2.02
Operating Guide ECL Comfort 310, application A333