MENU > Settings > Alarm
Alarm high (A333.2 / A333.3)
16614
Circuit
Setting range
Factory setting
1
0.0 . . . 25.0 m
25.0 m
Alarm is activated when the refill water storage tank level (in meter) gets
higher than the set value.
See also: "Alarm low" (ID no. 16615) and "Alarm time-out" (ID no. 16617).
0.0 - 25.0:
Set the high alarm level
When the "Alarm high" or "Alarm Low" alarm is activated:
*
the alarm symbol appears in the display
*
the refill water tank valve V3 closes
*
the refill water valve V1 closes
*
the refill water pump stops
If the alarm reason disappears:
*
the alarm must be reset manually
Resetting an alarm:
MENU > Alarm > Alarm overview > "5: Refill tank": Push dial
MENU > Settings > Alarm
Alarm low (A333.2 / A333.3)
16615
Circuit
Setting range
Factory setting
1
0.0 . . . 25.0 m
0.0 m
Alarm is activated when the refill water storage tank level (in meter) gets
lower than the set value.
See also: "Alarm high" (ID no. 16614) and "Alarm time-out" (ID no. 16617).
0.0 - 25.0:
Set the low alarm level.
X
= Time
Y
= Level
# 1 # = Actual level
# 2 # = Alarm high
# 3 # = Alarm low
# 4 # = Alarm time-out
126 | © Danfoss | 2017.09
VI.GU.T2.02
Operating Guide ECL Comfort 310, application A333