5.12.1 Differentiated heat cut-out
To set differentiated cut-out parameters for a heating circuit for
“Summer” and “Winter” go to “Heat cut-out”:
(MENU > Settings > Heat cut-out)
This function is active when the dates for “Summer” and “Winter”
are different in the “Heat cut-out” menu.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Heat cut-out
Extended heat cut-out setting
Parameter
ID
Setting range
Factory
setting
Summer day
1x393
*
*
Summer month
1x392
*
*
Summer cut-out
1x179
*
*
Summer filter
1x395
*
*
See Appendix “Parameter ID overview”
MENU > Settings > Heat cut-out
Extended winter cut-out setting
Parameter
ID
Setting range
Factory
setting
Winter day
1x397
*
*
Winter month
1x396
*
*
Winter cut-out
1x398
*
*
Winter filter
1x399
*
*
See Appendix “Parameter ID overview”
The above settings of the dates for the cut-out function are only
to be done in the heating circuit 1 and are valid for other heating
circuits in the controller as well, if applicable.
The cut-out temperatures as well as the filter constant are to be set
individually per heating circuit.
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
VI.LG.H4.02
© Danfoss | 2017.05 | 109
Operating Guide ECL Comfort 210/296/310, application A230