Danfoss scroll compressors
DSF
Instructions
2 | AN309640488445en-000201 - 8510290P02B
© Danfoss | DCS (CC) | 2020.10
The compressor must only be used for its
designed purpose(s) and within its scope of
application (refer to «operating limits»).
Consult Application guidelines and datasheet
available from cc.danfoss.com
Under all circumstances,
the EN378 (or other
applicable local safety
regulation) requirements
must be fulfilled.
The compressor is delivered under
nitrogen gas pressure (between 0.3 and
0.7 bar) and hence cannot be connected
as is; refer to the «assembly»
section for
further details.
The compressor must be
handled with caution in the
vertical position (maximum
offset from the vertical : 15°)
Installation and servicing of the compressor by
qualified personnel only. Follow these instructions and
sound refrigeration engineering practice relating to
installation, commissioning, maintenance and service.
A
: Model number
B
: Serial number
C
: Refrigerant
D
: Supply voltage, Starting current & Maximum operating current
E
: Housing service pressure
F
: Factory charged lubricant
1 – Introduction
These instructions pertain to the Danfoss scroll compressors DSF scroll com-
pressors used for air-conditioning systems. They provide necessary informa-
tion regarding safety and proper usage of this product.
DSF Large Operating map
3 - Operating map
2- Nameplate
Model no:
DSF485A4ABA
Serial no:
ZQ1109974321
MADE IN FRANCE
M
400V 3~50Hz
LR 343 A MAX OPER.92 A
Thermally protected system
P.E.D.
Marking
PS
TS MAX
TS MIN
Volume
Lubricant: 185 SL
Refrigerant: R32
PROTECTED BY DOMESTIC AND FOREIGN PATENTS
2019
LP Side
31,2 bar
51,0 °C
-35,0 °C
27,5 L
48,7 bar
150,0 °C
-35,0 °C
3,9 L
HP Side
0038
1234799011
A
D
E
F
B
C
C
ondensing t
emper
a
tur
e (°C
)
Evaporating temperature (°C)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
SH: 10 K
SH: 5 K