Akva Vita TDP-F - district heating flat station for direct HE and DHW

Instructions

DH-SMT/PL

VI.KR.Z1.02  ©

  Danfoss 09/2006

4

Pipes connections

Internal installation and district heating* pipes 

connections must be made by means of threaded 

or welded connections.

Connections:

1  District heating (DH) supply

2   District heating (DH) return

3   Domestic cold water (DCW) inlet

4   Domestic cold water (DCW) outlet

5   Domestic hot water (DHW)

6   Heating (HE) supply

7   Heating (HE) return

8   Circulation - optional

Connection sizes:

DH + DCW + DHW: 

G ¾” (int. thread)

HE + optional circ.: 

G ¾” (int. thread)

Dimensions (mm):

Without cover:

H 640 x W 565 x D 110 (incl. ball valves)

H 520 x W 565 x D 110 (excl. ball valves)

With cover:

H 740 x W 600 x D 150

*  District heating (DH) - In the following 

DH is specified as the heat source for the 

substations. However, also other heat sources 

such as an oil or gas boiler or solar heating 

etc. could be used as the primary supply for 

the fitted substations, enabling the Danfoss 

Redan substations to be used in numerous 

schemes with different energy sources, 

depending on the local operating conditions. 

In order to simplify we have decided to use 

DH as designation for the primary supply.

Electrical connection

The flat station needs no electrical installation to 

the main supply or earth grounding.

Filling, start-up

Prior to the Akva Vita TDP-F installation all its pipes 

and connections should be cleaned and rinsed.

Before starting-up, check if:

- pipes are connected according to the circuit 

diagram,

- release valves are shut-off,

- threaded connections are tightened.

The  heat  exchanger  must  be  filled  with  water 

so that the pressure slowly reaches the working 

pressure. 

After that the shut-off valves should be opened 

and the operation of the heat exchanger must be 

observed (e.g. temperatures, pressure, thermal 

expansion, leakages). If the heat exchanger operates 

operates unproblematically, it can be taken into 

continuous use. 

All Danfoss heat exchangers and flat stations have 

been pressure tested prior to delivery.

Содержание Akva Vita TDP-F

Страница 1: ...s DH SMT PL VI KR Z1 02 Danfoss 09 2006 1 Akva Vita TDP F Table of contents Akva Vita TDP F 1 Table of contents 1 Safety notes 2 Delivery 2 Transport and storage 2 Mounting 3 Pipes connections 4 Elect...

Страница 2: ...he at station has not been damaged during transport Noise level 55 dB Corrosion protection All pipes and components are made of stainless steel and brass The maximum chloride compounds of the ow mediu...

Страница 3: ...pillary tube with union nut from pos 3 to pos 2 Screw the conical screw from pos 2 4 mm on to the mu at pos 3 Connect circulation installation system with connection pipe for circulation Remember pump...

Страница 4: ...s the primary supply for the tted substations enabling the Danfoss Redan substations to be used in numerous schemes with di erent energy sources depending on the local operating conditions In order to...

Страница 5: ...be equipped with an electronic programmable room thermostat and a zone valve with actuator In this case temperature is controlled by the room thermostat and radiator thermostats Please note that the r...

Страница 6: ...If it is not possible to set the temperature according to the above recommendations it is recommended to change the standard controller setting PM controller The PM controller can operate in three ba...

Страница 7: ...1 20 C 2 30 C 3 40 C 4 45 C I 50 C max temp 5 Filters Filtersshouldfrequentlybecleanedfromsediments by authorized personnel according to producer s instructions and depending on the at station s oper...

Страница 8: ...logged Defective non return valve in thermostatic battery DHW tap temperature lower than DHW from at station Defective non return valve in hot water circulation circulation return pipe is getting cold...

Страница 9: ...t in the zone valve housing Air pockets in the system Clean gate strainer Clean the lter after consulting the district heating plant Check the operation of the di erential pressure controller clean th...

Страница 10: ...33 35 DK 8240 Risskov Denmark Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk Akva Vita TDP F district heating at station for direct HE and DHW Instructions DH SMT PL VI...

Отзывы: