background image

8

DKDHR 

VI.GP.N2.02 

Danfoss District Energy

Instructions   Water 

Heaters

10.0 Mounting

10.1 Test and connections

Check and tighten all connections before adding water to the system, 

as vibrations during transport may have caused leaks.  

After having added water to the system, tighten all the connections 

before performing leak test. If the water heater operates in accord-

ance with the dimensioning basis, re-tighten the connections and 

take the water heater into continuous use. 

NB!

Please note that the connections may be supplied with EPDM rubber 

gaskets.

 Therefore take care not to overstrain the union nuts, as 

this may result in leaks.

 The manufacturer accepts no liability for 

leaks that result from overstrain of union nuts.

10.2 Systems with domestic hot water (DHW) recirculation

If the household plumbing system includes hot water recirculation 

the water heater must be connected to the hot water recirculation 

system. 

Circulation set is not included in the delivery and must be ordered 

separately.

It is to be recommended to prepare the substation for recirculation 

before mounting it on the wall.

The recirculation pipe in your household plumbing system must 

be connected to a nipple, mounted on the circulation pipe of the 

substation. - 

See pages 9 to 12 for information about preparation 

of substation for and connection to the DHW recirculation system.

Remember always to mount circulation pump and non-return 

valve on the circulation pipe and to mount safety valve on the 

DCW inlet. 

The pump must be installed so that the pump is pumping 

water towards the water heater.

If a time-controlled pump is used, it is to be recommended that the 

circulation water temperature is set to approx. 35 °C.

If the circulation pump (outside the unit) is switched off for a longer 

period, it is to be recommended that the Danfoss FJVR  thermostat 

is closed during the same period. 

NOTE!

Please note that water heaters with Danfoss AVE expanion unit 

must 

not

 be used on systems with DHW recirculation.

Necessary assembly, start-up and maintenance work must be 

performed by qualified and authorized personnel only, and always 

in compliance with local regulations and this instruction manual.

The water heater must be easily accessible, enabling maintenance 

work without undue discomfort.

The water heater is intended for wall mounting and the mount-

ing sheet on the back of the water heater has got holes for screw 

installation. Lift the water heater in the mounting plate and fix it 

to a solid wall, which has the necessary load-bearing capacity, in a 

workmanlike manner with two strong bolts, screws or expansion 

plugs. 

Note, 

The Akva Lux II  and Akva Les II water heaters

 are not me-

chanically fixed in the insulation back and must be handled by lifting 

in both pipes and insulation simultaneously.

All pipes and connections must be cleaned and rinsed before start-

up. After that the strainers should be cleaned.

A label for each of the different connections is placed on the water 

heater. Connect the water heater to the household system according 

to these symbols as well as the instructions in this manual.

Circulation pipe connection

Содержание Akva Lux II

Страница 1: ...GW Diagram example measurements and main components 6 9 0 Akva Vita II Diagram example measurements and main components 7 10 0 Mounting 8 10 1 Test and connections 8 10 2 Systems with domestic hot wat...

Страница 2: ...qualization of potentials should be effected according to local regulations Warning of hot surfaces Parts of the water heater may become hot and hot surfaces can cause serious burns Please be extremel...

Страница 3: ...ose all shut off valves before the water heater is connected to the household piping 03 IMPORTANT Tighten all connections as vibrations during trans port and handling may have caused leaks 04 For syst...

Страница 4: ...ion cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instr...

Страница 5: ...8 Insulation cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose...

Страница 6: ...6 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instruction on page 14 Ac...

Страница 7: ...ples 5 Brushed stainless steel cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instructions...

Страница 8: ...valve on the DCWinlet The pump must be installed so that the pump is pumping water towards the water heater If a time controlled pump is used it is to be recommended that the circulation water temper...

Страница 9: ...ater towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 in controll...

Страница 10: ...ail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of union nu...

Страница 11: ...towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 as shown Fig 4...

Страница 12: ...s shown Fig 8 Demount capillary tube from T piece Fig 9 Demount capillary tube from bypass thermostat Fig 10 Mount M8 x 1 screw plug F in T piece Fig 11 Fit new capillary tube G on nipple B by means o...

Страница 13: ...and Akva Les II are equipped with a by pass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermostat in pos 3 Ifthew...

Страница 14: ...rculation thermostat Bypass thermostat default AsastandardtheAkvaLuxIIGWisequippedwithabypassthermostat Danfoss FJVR 2 which ensures that hot water is produced immedi ately when tapping starts It is r...

Страница 15: ...ault As a standard the Akva Vita II is equipped with a bypass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermosta...

Страница 16: ...heatexchangersweakinhibited acid solutions e g 5 formic acetic or phosphoric acid may be used Deacidificationofgasketedplateheatexhanger AkvaLuxIIGW See page 16 Measuresaftermaintenancework After main...

Страница 17: ...t and be able to dissolve the fouling calification on the plates Great care must be taken to select a proper cleaning solution that does not damage plates or gaskets Example of cleaning 1 Drain produc...

Страница 18: ...l compressed dimension The bolts must not be slackened or tightened indiscriminately They must be loosened tightened alternately on the left and right side and in a crosswise pattern Loosening and tig...

Страница 19: ...the household piping REMEMBER to check all the mixer taps in the house Replace mixer tap or non return valve only Not enough pressure on the hot water Strainer in cold water meter or in the cold wate...

Страница 20: ...e during tapping Calified heat exchanger Short circuiting of defective heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Poor cooling Calified hea...

Страница 21: ...e used in accordance with our instructions EU Directives EMC Directive 2004 108 EEC EN 61000 6 1 2007 Electromagnetic compatibility Generic standard Immunity for residential commercial and light indus...

Страница 22: ...technical regulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for...

Страница 23: ...23 23 Danfoss District Energy VI GP N2 02 DKDHR Instructions Water Heaters...

Страница 24: ...Produced by Danfoss Redan A S 02 2014 VI GP N2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Отзывы: