AKD 2800
■
EMC emission
The following system results are achieved on a
system consisting of a AKD Series 2800 with
screened/armoured control cable, control box with
potentiometer, screened/armoured motor cable
and screened/armoured brake.
AKD 2803-2875
Emission
Industrial environment
Residential, commercial and light industry
EN 55011 class 1A
EN 55011 class 1B
Setup
Cable-borne
150 kHz- 30 MHz
Radiated
30 MHz - 1 GHz
Cable-borne
150 kHz - 30 MHz
Radiated
30 MHz - 1 GHz
400 V version with 1A
RFI filter
Yes
25 m
screened/armoured
Yes
25 m screened/ar-
moured
No
No
400 V version with 1A
RFI filter (R5: For IT
mains)
Yes
5 m
screened/armoured
Yes
5 m screened/ar-
moured
No
No
200 V version with 1A
RFI filter
1.
Yes
40 m
screened/armoured
Yes
40 m screened/ar-
moured
Yes
15 m screened/ar-
moured
No
200 V version with 1A
RFI filter (R4: For use
with RCD)
Yes
20 m
screened/armoured
Yes
20 m screened/ar-
moured
Yes
7 m screened/ar-
moured
No
400 V version with
1A+1B RFI filter
Yes
50 m
screened/armoured
Yes
50 m screened/ar-
moured
Yes
25 m screened/ar-
moured
No
200 V version with
1A+1B RFI filter
1.
Yes
100 m
screened/armoured
Yes
100 m
screened/armoured
Yes
40 m screened/ar-
moured
No
AKD 2880-2882
Emission
Industrial environment
Residential, commerce and light industry
EN 55011 class 1A
EN 55011 class 1B
Setup
Cable-borne
150 kHz- 30 MHz
Radiated
30 MHz - 1 GHz
Cable-borne
150 kHz - 30 MHz
Radiated
30 MHz - 1 GHz
400 V version with 1B
RFI filter
Yes
50 m
Yes
50 m
Yes
50 m
No
1. For AKD 2822-2840 3 x 200-240 V the same values
apply as for the 400 V version with 1A RFI filter.
•
EN 55011:
Emission
Limits and methods of measurement of
radio disturbance characteristics of industrial, scien-
tific and medical (ISM) high-frequency equipment.
Class 1A:
Equipment used in an industrial environment.
Class 1B:
Equipment used in areas with a public supply network
(residential, commerce and light industry).
NB!:
This is a product of the restricted sales
distribution class according to IEC61800-3.
In a domestic environment this product may
cause radio interference in which case the user may
be required to take adequate measures.
■
UL Standard
This device is UL-approved.
MG.28.H2.02 -
64