operation [0], i.e. via the control terminals, or
Local [1], i.e. via the control unit.
Set the control location to Local [1].
Local/remote operation = Local [1] Par. 002
Set the motor speed by adjusting the
Local reference
Local reference Parameter 003
■
Motor start
Press [Start] to start the motor. Set the motor speed
by adjusting parameter 003 Local reference.
Check whether the direction of rotation of the motor
shaft is clockwise. If not, exchange any two phases
on the motor cable. Press [STOP/RESET] to stop the
motor. Press [QUICK MENU] to return to display mode.
[QUICK MENU] + [+] keys must be pressed
simultaneously to give access to all parameters.
■
AKD Lon card
Requirements:
AKD 2800 must have software version (par
624)
1.32 or higher
AKD 5000 must have software version (par
624)
1.52 or higher
The AKD Lon card is RS485 based and must connect
to an RS485 Adap-Kool Lon network.
The card can be ordered as build-in with the AKD5000
and comes in an external box for the AKD2800.
AKD Lon connections:
The Lon card has two connections.
A 6-pole connector (only 1-4 is used) that connects
to the AKD. Connections are as follows:
AKD-Connections:
Lon card terminals
1
(Red +24V)
2
(White or Yellow
TX-, RX-)
3
(Black Com)
4
(Green TX+, RX+)
AKD terminals
12
69
39 or 20
68
The 3-pole connector for the Lon Communication:
Lon card terminals
1
2
3
Adap-Kool Lon
A
B
Shield
Connect the Adap-Kool Lon network to the removable
3-postion connector. Be careful to route the network
wires away from the AC power and motor wires.
Commissioning
Upon power up the lower red LED of the double LED
’
s,
next to the Lon connectors will initially be flashing red.
1. Set AKD address in parameter 500 in
the AKD (1 to 60)
2. Wait for about 1 min until the red LED goes
off. (card initialisation)
3. Press one of the service pin buttons
4. Wait for about 2 minutes (upload of
parameters to gateway)
5. Perform a "Net configuration" upload in AKM
and you should now find the AKD. Perform a
"AKC description" upload in AKM
6. Go to menu AKC -> Controllers in AKM and
you should find the AKD
■
Safety regulations
The voltage of the frequency converter
can be fatal whenever it is connected to
mains. Incorrect installation of the motor or
the frequency converter may lead to damage to the
equipment, serious personal injury or death.
Consequently, the provisions of this Quick Setup,
as well as national and local rules and safety
regulations, must be complied with.
Touching the electrical parts may be fatal, even
after the equipment has been disconnected from
mains: wait at least 4 min.
1. The mains supply to the frequency converter must
be disconnected if repair work is to be carried out.
2. The [STOP/RESET] key on the control panel of the
frequency converter does not disconnect the mains
supply and is thus not to be used as a safety switch.
MG.28.H2.02 -
4