AKD 2800
Programming
NB!:
If
Not active
[0] is selected, the motor cannot
be stopped by means of the [STOP]-key.
017 Local reset of trip
(LOCAL RESET)
Value:
Not active (DISABLE)
[0]
✭
Active (ENABLE)
[1]
Function:
In this parameter, the reset function on the control
panel can be engaged/disengaged.
Description of choice:
If
Not active
[0] is selected in this parameter, the
reset function will be inactive.
NB!:
Select
Not active
[0], only if an external reset
signal has been connected via the digital inputs.
018 Lock for data changes
(DATA CHANGE LOCK)
Value:
✭
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
In this parameter, it is possible to
’
lock
’
the controls
to disable data changes via the control keys.
Description of choice:
If
Locked
[1] is selected, data changes in the
parameters cannot be made; however, it will
still be possible to make data changes via serial
communication. Parameter 009-012
Display readout
can be changed via the control panel.
024 Userdefined Quick Menu
(USER QUICKMENU)
Value:
✭
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select the standard
setup of the Quick menu key on the control panel
and the LCP 2 control panel.
Using this function, in parameter 025
Quick Menu
setup
the user can select up to 20 parameters
for the Quick Menu key.
Description of choice:
If
not active
[0] is selected, the standard setup
of the Quick Menu key is active.
If
Active
[1] is selected, the user-defined
Quick Menu is active.
025 Quick Menu setup
(QUICK MENU SETUP)
Value:
[Index 1 - 20] Value: 0 - 999
✭
000
Function:
In this parameter you define which parameters are
required in the Quick Menu when parameter 024
User-defined Quick Menu
is set to
Active
[1]´.
Up to 20 parameters can be selected for the
user-defined Quick Menu.
NB!:
Please note that this parameter can only be set
using an LCP 2 control panel. See
Order form
.
Description of choice:
The Quick Menu is set up as follows:
1. Select parameter 025
Quick Menu setup
and press [CHANGE DATA].
2. Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index numbers
using the [+ / -] keys. Select Index 1.
3. Using [< >] you can scroll between the
three figures. Press the [<] key once ad
the last number in the parameter number
can be selected using the [+ / -] keys.
Set Index 1 to 100 for parameter 100
Configuration
.
4. Press [OK] when Index 1 has been set to 100.
5. Repeat steps 2 - 4 until all parameters required
have been set to the Quick Menu key.
6. Press [OK] to complete the Quick Menu setup.
If parameter 100
Configuration
is selected at Index
1, Quick Menu will start with this parameter every
time Quick Menu is activated.
Please note that parameter 024
User-defined Quick
Menu
and parameter 025
Quick Menu setup
are reset
to the factory setting during initialisation.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.H2.02 -