Operating Guide
AK-SM 800
Страница 1: ...Operating Guide AK SM 800...
Страница 2: ...red before the alarm system will function properly again for the given device Replace the controller and reconnect the field communication line from the System Manager to the new device Configure the...
Страница 3: ...uits Mismatch is shown next to the newly added device to indicate that a wrong configuration file is in use for the newly added device Ensure the Show only scanned Devices is set to Yes 3 Setup the ne...
Страница 4: ...confirm that the Uncfg is gone after having installed the correct EDF file and reconfigured the new device 5 Reset system The above flow is executed via StoreView Desktop It is also possible to compl...