User Guide
|
Optyma™ control AK-RC 111 single phase
© Danfoss | DCS (vt) | 2020.03
BC309238530328en-000101 | 9
4.9 Level 2 programming
(installer level)
4.10 List of Level 2 variables
(installer level)
To access the second programming level press the UP (
) and DOWN (
) keys and the LIGHT key
simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1. Select the variable to be modified by pressing the UP (
) and DOWN (
) keys.
When the parameter has been selected it is possible to:
2. View the setting by pressing the SET key.
3. Modify the setting by holding the SET key down and pressing the (
) or (
) key.
4. When configuration settings have been completed you can exit the menu by pressing the (
) and
(
) keys simultaneously and keeping them pressed until the room temperature reappears.
5. Changes are saved automatically when you exit the configuration menu.
6. Press the STAND-BY key to enable electronic control.
Variables Meaning
Value
Default
F3
Fan status with compressor off
0 = Fans run continuously
1 = Fans only run when
compressor is working
2 = Fans disabled
1
F4
Fan pause during defrost
0 = Fans run during defrost
1 = Fans do not run during
defrost
1
F6
Evaporator fans activation for air recirculation.
The fans activate for a time defined by F7 if they have
not started working for the F6 time. If activation time
coincides with the defrosting time, end of defrosting
is awaited.
0 – 240 min
0 = (function not activated)
0 min
F7
Evaporator fans duration for air recirculation.
Fans working time for F6
0 – 240 sec
10 sec
dE
Sensor presence
If the evaporator sensor is disabled defrosts are
carried out cyclically with period d0: defrosting ends
when an external device trips and closes the remote
defrost contact or when time
d3
expires.
0 = evaporator sensor present
1 = no evaporator sensor
0
d1
Defrost type
, cycle inversion (hot gas) or with heater
elements
0 = heating element
1 = hot gas
2 = heater with
temperature control
0
dPo
Defrost at Power On
0 = disabled
1 = defrost at power-on
(if possible)
0
dSE
Smart defrost
0 = disabled
1 = enabled
0
dSt
Smart defrost Setpoint (if dSE=1)
The counting of the time between the defrost is
incremented only if the compressor is ON and the
evaporator temperature is less than dSt.
-30 – 30 °C
1 °C
dFd
Display viewing during Defrost
0 = current temperature
1 = temperature at the
start of the defrost
2 = “DEF”
1
Ad
Modbus Network address
0 – 247
0
Bdr
Modbus baudrate
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 14400 baud
7 = 19200 baud
8 = 38400 baud
8
Prt
Modbus parity check
0 = none
1 = even
2 = odd
1
Ald
Minimum and maximum temperature
signalling and alarm display delay
0 – 240 min
120 min
C1
Minimum time between shutdown and
subsequent
switching on of the compressor.
0 – 15 min
0 min
CAL
Cold room sensor value correction
-10 – 10 °C
0 °C