AHF 005/010
Programming
■
General technical data
AHF 0xx
AHF 0xx
AHF 0xx
AHF 0xx
Nominal supply
voltage
U
L,N
[V]
380
≤
U
L,N
≤
415
440
≤
U
L,N
≤
480
500 V
690 V
Tolerance of the
actual supply
voltage
U
L
[V]
342
≤
U
L
≤
456
396
≤
U
L
≤
528
450
≤
U
L
≤
550
621
≤
U
L
≤
759
Supply
frequency
f
L,N
[Hz]
50 ± 5 %
60 ± 5 %
50 ± 5 %
50 ± 5 %
Overload
capability
1.6 for 60s
Efficiency
η
[%]
~ 98.8 %
THiD
[%]
AHF 005 < 5%
AHF 010 < 10%
cos
φ
of I
L
0.5 cap
0.8 cap
0.85 cap
0.99 cap
1.00
at 25% I
AHF,N
at 50% I
AHF,N
at 75% I
AHF,N
at 100% I
AHF,N
at 150% I
AHF,N
Power derating
[%/C]
[%/m]
104°F < Ta < 131°F => 1.5%/F (40°C < Ta < 55°C
=> 3%/C)
3280 ft altitude above sea level < h
≤
13,100 ft
altitude above sea level => 5% / 3280 ft (1000m
altitude above sea level.< h
≤
4000m altitude above
sea level => 5%/1000m)
NOTE
The reduction of the low harmonic current
emission to the rated THiD implies that the
THvD of the non-influenced line voltage is
lower than 2% and the ratio of short circuit power
to installed load (R
SCE
) is at least 66. Under these
conditions, the THiD of the line current of the adjustable
frequency drive is reduced to 10% or 5% (typical
values at nominal load). If these conditions are not
or only partially fulfilled, a significant reduction of the
harmonic components can still be achieved, but the
rated THiD values may not be achieved.
MG.80.B4.22 - VLT is a registered Danfoss trademark
7