AHF 005/010
Installation
■
Ordering numbers, 440 - 480 V, 60 Hz
Danfoss ordering number
Typical Danfoss adjustable frequency drive series
I
AHF,N
Typical Motor
Used [HP]
AHF 005
AHF 010
VLT 5000
VLT 6000 HVAC
VLT 8000 AQUA
19 A
10, 15
175G6612
175G6634
5011, 5016
6011, 6016
8011, 8016
26 A
20
175G6613
175G6635
5022
6022
8022
35 A
25, 30
175G6614
175G6636
5027, 5032
6027, 6032
8027, 8032
43 A
40
175G6615
175G6637
5042
6042
8042
72 A
50, 60
175G6616
175G6638
5052, 5062
6052, 6062
8052, 8062
101 A
75
175G6617
175G6639
5072
6072
8072
144 A
100, 125
175G6618
175G6640
5102, 5122
6102, 6122
8102, 8122
180 A
150
175G6619
175G6641
5152
6152
8152
217 A
200
175G6620
175G6642
5202
6172
8202
289 A
250
175G6621
175G6643
5252
6222
8252
324 A
300
175G6689
175G6692
5302
6272
8302
370 A
350
175G6690
175G6693
5352
6352
8352
Higher ratings can be achieved by paralleling the filter units
506 A
450
217 A and 289 A units
5452
6402
8452
578 A
500
Two 289 A units
5502
6502
8502
648 A
600
Two 324 A units
-
6552
8602
Please note that the matching of the typical Danfoss adjustable frequency drive and filter is pre-calculated
based on 480V and assuming typical motor load. VLT 5000 series is based on a 160 % torque application,
while VLT 6000 and 8000 series are based on 110% torque application.
The pre-calculated filter current may vary from the input current ratings of the VLT 5000, VLT 6000, and
VLT 8000 series as stated in the respective instruction manuals, as these numbers are based on different
operating conditions.
■
Ordering numbers, 500 V, 50 Hz
Danfoss ordering number
Typical Danfoss adjustable frequency drive series
I
AHF,N
Typical Motor
Used [kW]
AHF 005
AHF 010
VLT 5000
VLT 6000 HVAC
VLT 8000 AQUA
10 A
4, 5.5
175G6644
175G6656
5006, 5008
6006, 6008
8006, 8008
19 A
7.5, 11
175G6645
175G6657
5011, 5016
6011, 6016
8011, 8016
26 A
15, 18.5
175G6646
175G6658
5022, 5027
6022, 6027
8022, 8027
35 A
22
175G6647
175G6659
5032
6032
8032
43 A
30
175G6648
175G6660
5042
6042
8042
72 A
37, 45
175G6649
175G6661
5052, 5062
6052, 6062
8052, 8062
101 A
55, 75
175G6650
175G6662
5062, 5072
6062, 6072
8062, 8072
144 A
90, 110
175G6651
175G6663
5102, 5122
6102, 6122
8102, 8122
180 A
132
175G6652
175G6664
5152
6152
8152
217 A
160
175G6653
175G6665
5202
6172
8202
289 A
200
175G6654
175G6666
5252
6222
8252
324 A
250
175G6655
175G6667
5302
6302
8302
Higher ratings can be achieved by paralleling the filter units
434 A
315
Two 217 A units
5352
6352
8352
469 A
355
180 A and 289 A units
5452
6402
8452
578 A
400
Two 289 A units
5502
6502
8502
Please note that the matching of the typical Danfoss adjustable frequency drive and filter is pre-calculated
based on 500V and assuming typical motor load. VLT 5000 series is based on a 160 % torque application,
while VLT 6000 and 8000 series are based on 110% torque application.
The pre-calculated filter current may vary from the input current ratings of the VLT 5000, VLT 6000, and
VLT 8000 series as stated in the respective instruction manuals, as these numbers are based on different
operating conditions.