AHF 005/010
■
Mechanical installation
The encapsulation of the filters has an IP 20
rating. The modules can be mounted side-by-side
with 2.36 in. (60mm) clearance.
To other components and to the cabinet walls, maintain
a horizontal clearance of at least 2.76 in. (70mm) and a
vertical clearance of at least 5.91 in. (150mm).
Only vertical installation is allowed (line
terminal at bottom).
For versions with bus bars (frame size
E - H), it is necessary to mount the
added covers to the connectors in order
to achieve the protection type IP 20.
■
Ventilation
The filters are cooled by means of air circulation.
Consequently, the air needs to be able to move freely
above and below the filter module. The efficiency
of the filter modules is greater than 0.98. When
installing a filter module in a panel or another enclosure,
ensure there is sufficient airflow through the enclosure
to limit heat rise in the enclosure.
AHF 0xx, 380 – 415V
Max. Heat
AHF 0xx, 440 – 480V
Max. Heat
AHF 0xx, 500V
Max. Heat
AHF 0xx, 690V
Max. Heat
10 A
283 Btu/hr (83 W)
355 Btu/hr (104 W)
19 A
540 Btu/hr (158 W)
649 Btu/hr (190 W)
672 Btu/hr (197 W)
26 A
738 Btu/hr (216 W)
884 Btu/hr (259 W)
922 Btu/hr (270 W)
35 A
990 Btu/hr (290 W)
1192 Btu/hr (349 W)
1243 Btu/hr (364 W)
43 A
1223 Btu/hr (358 W)
1465 Btu/hr (429 W)
1526 Btu/hr (447 W)
2107 Btu/hr (617 W)
72 A
2046 Btu/hr (599 W)
2452 Btu/hr (718 W)
2554 Btu/hr (748 W)
3528 Btu/hr (1033 W)
101 A
2869 Btu/hr (840 W)
3442 Btu/hr (1008 W)
3586 Btu/hr (1050 W)
4945 Btu/hr (1448 W)
144 A
4088 Btu/hr (1197 W)
4907 Btu/hr (1437 W)
5109 Btu/hr (1496 W)
7052 Btu/hr (2065 W)
180 A
5109 Btu/hr (1496 W)
6133 Btu/hr (1796 W)
6389 Btu/hr (1871 W)
8814 Btu/hr (2581 W)
217 A
6161 Btu/hr (1804 W)
7393 Btu/hr (2165 W)
7701 Btu/hr (2255 W)
10,627 Btu/hr (3112
W)
289 A
8206 Btu/hr (2403 W)
9845 Btu/hr (2883 W)
10,255 Btu/hr (3003
W)
14,155 Btu/hr (4145
W)
324 A
9200 Btu/hr (2694 W)
11,037 Btu/hr (3232
W)
11,498 Btu/hr (3367
W)
15,866 Btu/hr (4646
W)
370 A
10,504 Btu/hr (3076
W)
12,605 Btu/hr (3691
W)
18,120 Btu/hr (5306
W)
NOTE
If other heat sources (e.g. Danfoss
adjustable frequency drives) are installed in
an enclosure with the harmonic filter AHF
0xx, this heat generation must also be considered
when calculating required airflow
NOTE
If the cooling air is polluted (dust, dirt swirl,
grease, aggressive gas), the function of
the filter module may be impeded. Ensure
sufficient countermeasures, e.g. separate cooling air,
mounting of air filters, periodical cleaning.