3.8.7 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e. Terminal 42. Analog outputs are current outputs: 0/4 – 20 mA. Common terminal
(terminal 39) is the same terminal and has the same electrical potential for analog common and digital common connection. Resolution on analog output
is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog current output. A motor current of 20 mA corre-
sponds to I
max
.
[0]
No operation
[100] *
Output frequency
: 0 - 100 Hz, (0-20 mA)
[101]
Reference
: Minimum reference - Maximum reference, (0-20 mA)
[102]
Feedback
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
, (0-20 mA)
[103]
Motor current
[104]
Torque rel to limit
: 0 - Torque limit (par.4-16
), (0-20 mA)
[105]
Torq relate to rated
: 0 - Motor rated torque, (0-20 mA)
[106]
Power
: 0 - Motor rated power, (0-20 mA)
[107]
Speed
: 0 - Speed High Limit (par.4-13
), (0-20 mA)
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[130]
Output freq. 4-20mA
: 0 - 100 Hz
[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par.16-37
[134]
Torq.% lim 4-20 mA
: 0 - Torque limit (par.4-16
[135]
Torq.% nom 4-20mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (4-13 and 4-14)
[138]
Torque 4-20mA
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA
: 0 - 100%
[143]
Ext. CL 1 4-20mA
: 0 - 100%
[144]
Ext. CL 2 4-20mA
: 0 - 100%
[145]
Ext. CL 3 4-20mA
: 0 - 100%
[150]
Max Out Fr 4-20 mA
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
90
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...