5-02 Terminal 29 Mode
Option:
Function:
[0] *
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
This parameter cannot be adjusted while the motor is running.
3.7.3 5-1* Digital Inputs
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the following functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 32, 33
Reset
[1]
All
Coast inverse
[2]
All
Coast and reset inverse
[3]
All
DC-brake inverse
[5]
All
Stop inverse
[6]
All
External interlock
[7]
All
Start
[8]
All *term 18
Latched start
[9]
All
Reversing
[10]
All *term 19
Start reversing
[11]
All
Jog
[14]
All *term 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Ramp bit 0
[34]
All
Mains failure inverse
[36]
All
Fire mode
[37]
Day/ Night Control
[39]
Run Permissive
[52]
Hand start
[53]
Auto start
[54]
DigiPot Increase
[55]
All
DigiPot Decrease
[56]
All
DigiPot Clear
[57]
All
Reset Counter A
[62]
All
Reset Counter B
[65]
All
Sleep Mode
[66]
Reset Maintenance Word
[78]
Lead Compressor Start
[120]
Lead Compressor Alternation
[121]
Compressor 1 Interlock
[130]
Compressor 2 Interlock
[131]
Compressor 3 Interlock
[132]
Comp. 1 Inv. Interlock
[139]
Comp. 2 Inv. Interlock
[140]
Comp. 3 Inv. Interlock
[141]
All = Terminals 18, 19, 27, 29, 32, X30/2, X30/3, X30/4. X30/ are the terminals on MCB 101.
Functions dedicated to only one digital input are stated in the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No operation
No reaction to signals transmitted to terminal.
[1]
Reset
Resets frequency converter after a TRIP/ALARM. Not all alarms can be reset.
[2]
Coast inverse
Leaves motor in free mode. Logic ‘0’ => coasting stop.
(Default Digital input 27): Coasting stop, inverted input (NC).
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
69
3