22-31 Power Correction Factor
Range:
Function:
100 %*
[1 - 400 %]
Make corrections to the calculated power at par.22-30
.
If No Flow is detected, when it should not be detected, the setting should be decreased. However,
if No Flow is not detected, when it should be detected, the setting should be increased to above
100%.
22-32 Low Speed [RPM]
Range:
Function:
0 RPM*
[0 - par. 22-36 RPM]
To be used if par.0-02
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 50% level.
This function is used for storing values needed to tune No Flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
0 Hz*
[0.0 - par. 22-37 Hz]
To be used if par.0-02
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 50% level.
The function is used for storing values needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
0 kW*
[0.00 - 0.00 kW]
To be used if par.0-03
has been set for International (parameter not visible if
North America selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
0 hp*
[0.00 - 0.00 hp]
To be used if par.0-03
has been set for North America (parameter not visible if
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
0 RPM*
[0 - par. 4-13 RPM]
To be used if par.0-02
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-37 High Speed [Hz]
Range:
Function:
0.0 Hz*
[0.0 - par. 4-14 Hz]
To be used if par.0-02
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
0 kW*
[0.00 - 0.00 kW]
To be used if par.0-03
has been set for International (parameter not visible if
North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
174
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...