No.
96
97
98
Motor voltage 0-100% of mains voltage.
U
V
W
3 cables out of motor
U1
V1
W1
6 cables out of motor, Delta-connected
W2
U2
V2
U1
V1
W1
6 cables out of motor, Star-connected
U2, V2, W2 to be interconnected separately
(optional
terminal
block)
No.
99
Earth connection
PE
Table 5.7 3 and 6 cable motor connection.
5.1.11 Motor Wiring Overview
Enclosure:
A2
(IP 20/IP 21)
A3
(IP 20/IP 21)
A4
(IP 55/IP 66)
A5
(IP 55/IP 66)
B1
(IP 21/IP 55/
IP 66)
B2
(IP 21/IP 55/
IP 66)
C1
(IP 21/IP
55/66)
C2
(IP 21/IP
55/66)
Motor size:
200-240 V
1.1-3.0
kW
3.7
kW
0.25-2.2
kW
1.1-3.7
kW
5.5-11
kW
15
kW
18.5-30
kW
37-45
kW
380-480 V
1.1-4.0
kW
5.5-7.5
kW
0.37-4.0
kW
1.1-7.5
kW
11-18.5
kW
22-30
kW
37-55
kW
75-90
kW
Goto:
5.1.12
5.1.13
5.1.13
5.1.14
5.1.15
Table 5.8 Motor wiring table.
Electrical Installation
ADAP-KOOL
®
Drive Operating Instructions
36
MG.11.L4.02 - ADAP-KOOL
®
Drive
5