Installing the Top Panel Cover
1.
Cut out the 2 exhaust vent openings in the top panel
cover. The openings must match to the exhaust vent
openings on the upper duct assembly. Refer to
Illustration 1.9
.
2.
Secure the top panel cover to the frame.
Illustration 1.9 Vent Dimensions for the Top Panel Cover
Installing the Back Cover Panel
1.
Install a gasket (2) around each vent opening on the
back side of the mounting backplate (1). Refer to
Illustration 1.10
.
2.
Install a duct spacer (3) onto each of the gaskets.
Secure each duct spacer with 6 M5 nuts. Torque to
5.1 Nm (45 in-lb).
3.
Place a gasket (4) onto each duct spacer.
1
Mounting backplate
2
Gasket between the mounting backplate and duct spacer
3
Duct spacer
4
Gasket between the duct spacer and back cover panel
Illustration 1.10 Installing the Duct Spacers
4.
Prepare the back cover panel. Refer to
Illustration 1.11
.
4a
Cut out the 2 intake vent openings in the
back cover panel. The openings must match
to the intake vent openings on the intake
duct spacer.
4b
Drill the 8 screw holes around the vent
openings.
5.
Secure the back cover cabinet panel to the frame.
6.
Secure the back cover panel to the duct spacers with
8 M5x16 screws. Torque to 5.1 Nm (45 in-lb).
Illustration 1.11 Vent Dimensions for the Back Cover Panel
Installation Instructions
In-back/Out-top Cooling Kit for VLT
®
Parallel Drive Modules
VLT
®
Series FC 102, FC 202, and FC 302
MI92K102
Danfoss A/S © 04/2016 All rights reserved.
9