Advanced Configuration
S200-VTS Product Manual
89
EncOutZOffset 0 to 65535 Counts
Supported over SynqNet.
EncOutZOffset sets the location of the emulated encoder marker or Z-pulse on the J4-17,18 CH
Z OUT. Base unit (PosFB – EncOutZOffset) is sent to the decoding logic to make the CH Z
OUT so EncOutZOffset allows electronically setting the exact mechanical location for the
emulated Z pulse. See diagram for exact phase of the Z-pulse.
Encoder Phasing for Clockwise Motor Rotation
Z
B
A
PosFB – EncOutZoffset = 0
EnInhibitCCW On or Off
Not supported over SynqNet.
Enables or disables the hardware input that prevents motion in the counter clockwise direction.
When enabled and the hardware input is active, current/torque operation clamps the current
command to 0 or positive/clockwise. With a velocity loop, function enabled, and the hardware
input active, the velocity command is clamped to 0 or positive/clockwise. When both
InhibitCCW and InhibitCW are enabled and both hardware inputs are active, the motion
command is clamped to 0.
0 - OFF
1 - ON
EnInhibitCW On or Off
Not supported over SynqNet.
Enables or disables the hardware input that prevents motion in the clockwise direction. When
enabled and the hardware input is active, current/torque operation clamps the current
command to be 0 or negative/counter clockwise. With a velocity loop, function enabled, and the
hardware input active the velocity command is clamped to be 0 or negative/counter clockwise.
When both InhibitCCW and InhibitCW are enabled and both hardware inputs are active, the
motion command is clamped to 0.
0 - OFF
1 - ON
FBSrc Base Unit Feedback, Option Card Feedback
(Option Card Only)
Supported over SynqNet.
Enables When this bit is set to the Option Card Feedback position, it disables both the SFD and
Hall feedback faults and device interfaces on the base unit. This bit also forces the feedback
position word from the SFD to be zero. The drive is set for sine commutation. In this mode,
writing to the CommOff parameter will change the motor position. This mode is used when an
Option card is attached and the primary feedback device is a Comcoder.
0 - Base Unit feedback device connected.
1 - Option card feedback device connected.
FltDiag Off or Diagnostic Blink Code
FltDiag selects between the DOUT1 (Fault) line being static low for no fault and static high for
drive off and/or faulted, to low for no fault and toggle high low N number of times with the
diagnostic LED fault blink code. The DOUT1 line output is still static high for drive off. See
FaultCode entry for a chart giving the blink counts for each fault.
0 - OFF (default)
1 - Diagnostic Blink Code