Basic Configuration
S200-VTS Product Manual
71
7.3
Configuring with 6-Step (Hall) Feedback
7.3.1
6-Step Feedback Wiring
1
2
HALL
1
2
3
4
FEE
D
B
A
C
K
6
5
4
3
M OTOR
+5 RTN
+5V
CU
CV
CW
J3
J2
MO
T
O
R
PO
W
E
R
PHASE U
PHASE V
PHASE W
PE
7.3.2
6-Step Torque/Current Mode
In 6-Step mode with Hall or Hall equivalent feedback, the drive can be configured either using
the S200Tools utility or the S1 and S2 switches. Configuring the drive with the S200 Tools
provides the advantage of setting the drive's current limits and motor thermal protection. When
using S200Tools the configuration parameters should be saved to non-volatile memory to allow
the configuration to be recalled on power up.
To configure the drive for 6-Step feedback set the following parameters:
Parameter Value
CommMode
SetupS2-2 (Default value) with switch S2-2 set to the up position labeled,
6
on
the drive.
or
6-Step
CommOff
0 Degrees (Default value)
OpMode
SetupS2-1 (Default value) with switch S2-1 set to the down position labeled,
I
on the drive.
or
Torque/Current
KIP
Set directly with the serial port when S1 is set to position 0
or
Set S1 to the appropriate position for the inductance of the motor be used,
refer to Configuring Current Mode with 6-Step (Hall) Feedback.
I2TF0
Set to the motor’s thermal time constant.
I2TTrip
Set to the motor’s continuous current rating.
ILmtPlus
ILmtMinus
Set to the lower of 100% or the percent of the motor’s peak current rating
divided by the drives peak current.
CmdSrc
Sets the source of the command, analog or command variable.
CmdGain
Sets the command gain for the command input.
CmdOffset
Sets the command offset for the command input.
CmdF0
Sets the filtering on analog input commands.