Basic Configuration
05/2008
Danaher Motion
68
S200-VTS Product Manual
7.1.2.2
S1 Function with 6-Step Feedback
In 6-step mode, S1 sets the current loop proportional gain, KIP. Set S1 to the value listed in the
table for your drive type and motor inductance. Consult the factory if the motor inductance is
lower or higher than what can be accommodated by S1. An incorrect setting of KIP can cause
current loop instability or oscillation potentially resulting in damage to the drive or application.
Motor Inductance Table for 6-Step Commutation (L in mH)
AC Input Drive
DC Input Drive
S1
S20260 S20360 S20660 S20330 S20630 Position
User
Settable
1
(factory
default =
96.932)
User
Settable
1
(factory
default =
48.416)
User
Settable
1
(factory
default =
24.208)
User
Settable
1
(factory
default =
12.104)
User
Settable
1
(factory
default =
6.052) 0
1
6.17 - 9.03 3.09 - 4.50 1.55 - 2.25
0.52 - 0.75
0.27 - 0.38
1
9.04 -
13.39
4.51 - 6.69 2.26 - 3.34
0.76 - 1.11
0.39 - 0.56
2
13.40 -
19.56
6.70 - 9.78 3.35 - 4.89
1.12 - 1.63
0.57 - 0.81
3
19.57 -
28.89
9.79 -
14.44
4.90 - 7.22
1.64 - 2.41
0.82 - 1.20
4
28.90 -
43.34
14.45 -
21.67
7.23 -
10.83
2.42 - 3.61
1.21 - 1.80
5
43.35 -
63.80
21.68 -
31.90
10.84 -
15.95
3.62 - 5.32
1.81 - 2.65
6
63.81 -
95.11
31.91 -
47.55
15.96 -
23.76
5.33 - 7.92
2.66 - 3.96
7
95.12 -
144.49
47.56 -
72.24
23.77 -
36.12
7.93 -
12.04
3.97 - 6.02
8
144.50 -
216.74
72.25 -
108.4
36.13 -
54.20
12.05 -
18.06
6.03 - 9.03
9
1
S1 position 0 allows setting the non-volatile KIP via the serial port to any
valid value in 6-Step mode. The value written will replace the default value
listed in position 0 of the table.
7.1.3
S11, S12 - Rotary SynqNet ID Switches
The SynqNet ID switches can be used to help distinguish and differentiate a drive on the
network by assigning a unique ID to the drive.
To set a SynqNet ID to an S200 drive, turn the S11 LSB (Least Significant Bit) and S12 MSB
(Most Significant Bit) switches to a desired letter/number combination.
The SynqNet ID can then be read using the following utilities: Motion Console and Version.exe
Utility.