Specifications 05/2008 Danaher
Motion
12
S200-VTS Product Manual
3.2
AC Input Drives - Control and Power
3.2.1
AC Control Power Supply
Input Voltage Range (RMS)
85 VAC to 265 VAC 1 phase 47 to 410 Hz
Or 120 VDC to 375 VDC
Ride Through Time for AC
Line Drop
85 VAC 60 Hz > 0.78 60 Hz cycles
120 VAC 60 Hz > 3.3 60 Hz cycles
240 VAC 60 Hz >18.5 60 Hz cycles
3.2.2
AC Motor Power Supply
Input Voltage Range (RMS)
S20260, S20360, S20660: 0 to 265 VAC
S21260, S22460: 120 to 265 VAC
Phases
1 or 3
Transformer Suggested KVA
S20260: 1.5 to 2 kVA
S20360: 2.0 to 3 kVA
S20660: 3.0 to 5 kVA
S21260: 4.5 to 6 kVA
S22460: 8.0 to 12 kVA
Maximum AC Line KVA
1
S20260, S20360, S20660: 100
S21260, S22460: 250
1
Maximum AC Line is specified to limit the mains surges to the drive.
3.2.3
AC Bus Voltage and Faults
240 VAC Input Nominal Bus
Voltage
320 VDC
120 VAC Input Nominal Bus
Voltage
155 VDC
BUS Undervoltage Fault
S20260, S20360, S20660 Default is None
S21260, S22460: 150 VDC
BUS Overvoltge (BusOV)
Fault
407 VDC + 5%
BUS Regen Voltage
= 0.974*BusOV = 397 VDC Nominal
3.2.4
AC Motor Power Inrush Current & Fusing
S20260 S20360 S20660
S21260,
S22460
Worse Case Inrush Peak
Current at 240 VAC
140 A 0-p
140 A 0-p
240 A 0-p
None, soft
start
Inrush pulse width
1.5 ms
1.5 ms
2.0 ms
NA
Recommended
Fusing Line Inputs
S20260 S20360 S20660 S21260 S22460
Type – 250 VAC Time Delay Fuse
240 VAC 3 Phase
(ARMS)
Bussmann
FRN-R-5
Bussmann
FRN-R -8
Bussmann
FRN-R -15
Bussmann
JKS-20
Bussmann
JKS-30
240 VAC 1 Phase
(ARMS)
Bussmann
FRN-R -5
Bussmann
FRN-R -10
Bussmann
FRN-R -20
Bussmann
JKS-30
Bussmann
JKS-30
120 VAC 1 Phase
(ARMS)
Bussmann
FRN-R -5
Bussmann
FRN-R -10
Bussmann
FRN-R -20
NA NA