Installation / Commissioning
II.1
Important notes
l
Check that the servo-amplifier and motor match each other. Compare the rated
voltage and rated current of the unit. Carry out the wiring according to the wiring
diagram in the Installation and Commissioning Instructions for the servo-amplifier.
The connections to the motor are shown on pages 17f. Notes on the connection
methods can be found on page 16.
l
Ensure that there is proper earthing of the servo-amplifier and the motor.
l
Route the power and control cables as separately as possible from one another
(separation > 20 cm). This will improve the immunity of the system to electromag-
netic interference.
If a motor power cable is used which includes integral brake control leads, then
these brake control leads must be shielded. The shielding must be connected at
both ends (see under Installation Instructions for the servo-amplifier).
l
Install all cables carrying a heavy current with an adequate cross-section, as per
EN 60204. The recommended cross-section can be found in the Technical data.
Caution!
If a servo-amplifier of the series SERVOSTAR™ 601 ..620 is used and the mo-
tor cable exceeds 25m, a boxed choke (type 3YL-xx, manufactured by
Danaher Motion) and motor leads with the following diameters must be used:
Servo amplifier
Choke box
Max. diameter of the motor lead
SERVOSTAR™ 601...606
3YL-20
4 x 1mm²
SERVOSTAR™ 610
3YL-20
4 x 1,5mm²
SERVOSTAR™ 620
3YL-20
4 x 2,5 mm²
l
Connect up all shielding via a wide surface-area contact (low impedance) and
metallized connector housings or EMC-cable glands.
l
Check the compliance to the permitted radial and axial forces F
R
and F
A
.
When you use a toothed belt drive, the
minimal
permitted diameter of the pinion
e.g. follows from the equation:
d
M
F
R
min
³
´
0
2.
l
Ensure that there is adequate heat transfer in the surroundings and the motor
flange, so that the maximum permissible flange temperature is not exceeded in S1
operation.
Caution!
Never undo the electrical connections to the motor while it is energised. A
dangerous voltage, resulting from residual charge, can be still present on the
capacitors up to 5 minutes after switch-off of the mains supply.
Measure the DC-link voltage and wait until it has fallen below 40V.
Even when the motor is not rotating, control and power leads may be live.
Motor series DBL/DBK
13
Danaher Motion
05/2001
Installation / Commissioning
Содержание DBL Series
Страница 12: ...I 7 1 Model number description In preparation 12 Motor series DBL DBK General 05 2001 Danaher Motion...
Страница 25: ...This page has been deliberately left blank Motor series DBL DBK 25 Danaher Motion 05 2001 Technical data...
Страница 29: ...DBL2H00080 Motor series DBL DBK 29 Danaher Motion 05 2001 A 4 044 3 03 Technical data...
Страница 45: ...This page has been deliberately left blank Motor series DBL DBK 45 Danaher Motion 05 2001 Technical data...
Страница 49: ...This page has been deliberately left blank Motor series DBL DBK 49 Danaher Motion 05 2001 Technical data...
Страница 53: ...DBL8L09300 DBL8L11500 Motor series DBL DBK 53 Danaher Motion 05 2001 A 4 044 3 31 32 Technical data...
Страница 57: ...DBK4N00160 DBK4H00160 Motor series DBL DBK 57 Danaher Motion 05 2001 A 4 044 3 45 46 Technical data...
Страница 61: ...DBK5H00430 Motor series DBL DBK 61 Danaher Motion 05 2001 A 4 044 3 48 Technical data...
Страница 65: ...This page has been deliberately left blank Motor series DBL DBK 65 Danaher Motion 05 2001 Technical data...