The programmable parameters
Menu A : Inverter Related Parameters
Access in STOP mode only by entering
2ndF A
Display
Description
Values
Max. current.
(A) =
Display the maximum output current of the
inverter. This parameter is related to the drive
rating and is used to protect the drive in overload
conditions as well short circuit between phases
and phase to ground.
K4005 = 10 A
K4010 = 15 A
K4015 = 23 A
K4020 = 30 A
K4030 = 45 A
K4040 = 60 A
K4060 = 90 A
K4090 = 135 A
K4120 = 180 A
Softwareversion
V-
Release number of the installed software.
In case of programming problems, please indicate
this number when calling our customer support.
V.xx.x
Date of delivery
Shipping date of the unit. This is the date the unit
left our manufacturing plant in Switzerland.
?
Serial number
K-
Specific to each unit. The first 4 digits “xxxx” are
related to the power rating of the units. The
yyyyy.zz are related to our internal codification.
Kxxxx.yyyyy.zz
Running timer
(h)=
Cumulated time in START mode
0.0 H
Time power
applied (h)=
Cumulated time input voltage ON
0.0 H
The Menu A is a read only
. No information can be modified by the customer
Menu B – Part 1: Operation related parameters
Access in STOP mode only
Display
Description
0=F 1=GB 2=D 3=I 4=E
Selection of the user language. Enter:
•
0 for French
•
1 for English
•
2 for German
•
3 for Spanish
•
4 for Italian
For the time being only English, German and French manuals
are available.
Menu locking
0=B,C 1=B
→
F,J
Locking the acces to menus, using terminals X2/47-48
0
Locking acces to menus B and C
1
Locking access to menus B, C, D, E, F, J
Only menus G (Display), H (faults list) and I (Reset)
remain
accessible
CAUTION:
The STOP key of the keypad is always active.
Start/Stop (choice)
0=PC560 1=T.Bl.?
The START / STOP function can be assigned to:
0
K
EY
P
AD
PC560
1
T
ERMINAL
B
LOC
X2
This allocation is an “OR” function for the START, but an “AND”
function for the STOP, the STOP key on the K
EY
P
AD
being
always active.
Speed display units
0=Hz 1=rpm ?
Here you pre-set the displayed units for the speed.
•
Enter
0
for
Hz
•
1
for
RPM
, the number of poles of the motor will be taken into
consideration automatically.
S476-gb-0348
User Manual K4000
Page 29 / 48