www.dalemans.com
|
14
3.4.
Connection to a DALEMANS control unit
For instructions about the electrical connection of the control unit, please refer
to the original equipment instruction manual.
The connection of the
DAT 420
gas detector to a DALEMANS control unit requires a 2-wire cur-
rent loop. The electrical connection must be made with respect to polarity between the detector
and the control unit.
To connect the
DAT 420
gas detector to a DALEMANS control unit:
▪
Loosen the locking screw of the junction box cover using the 1.5 mm hex key and completely
turn the cover counterclockwise to unscrew it.
▪
Loosen the cable gland cap nut, insert the cable into the cable gland and tighten.
▪
Connect the wires to the 2-position terminal block according to the diagram below.
▪
The cable wires must be stripped and plugged so that the gap between the wire insulation
and the metal edge of the terminal connection does not exceed 1 mm distance.
▪
Equipotential bonding may be provided using either the internal or the external connection.
For the external connection, the bonding conductor should be at least 4 mm².
▪
Screw the cover back onto the junction box and hand tighten ¼ turn.
▪
Put the locking screw of the cover back in place and tighten with the 1.5 mm hex key.
▪
The cable shielding or screening must be grounded at the control unit.
Figure 7: connection to a DALEMANS control unit
Connections for
equipotential
bonding