Adeo Control SGDD-C4-4
Manual
Rev. 1.6
Adeo Control is a brand of Adeo Group s.r.l.
17
/
36
18.
Telnet
The gateway has a Telnet server that can receive and/or transmit a DMX512A/DALI/MODBUS
RTU universe from/to other devices via TCP protocol, in our case to the Control4 driver.
Communication takes place by establishing a connection on
TCP port 23
(Do not change).
The minimum interval that can be set for sending the response strings is defined as
Minimum
scan time
.
If no changes are detected, the interval at which the string is periodically sent is defined with the
value set to Maximum scan time. A value of zero disables periodic transmission.
The tests were carried out on the basis of the default settings. The variation may lead to changes
in the integration behavior.
19.
ARTNet
The gateway implements the Art-Net 4 protocol and can be used as a gateway by the main
software and lighting control systems:
•
Art-Net
→
DMX
•
Art-Net
→
DALI
The port used is there UDP 6454.
After changing the settings, click on the top right button "
APPLY
" otherwise the changes will be
lost.
20.
MODUBUS TCP Slave
The gateway has a
MODBUS TCP/IP
server capable of receiving and/or transmitting a DMX512A
universe to one or more Modbus devices on an Ethernet network. 512 registers are available, with
Modbus address from 0 to 511 and value from 0 to 255.
The port used is
UDP 502
, the
Slave ID
is not taken into account.
After changing the settings click on the top right button "
APPLY
" otherwise the changes will be
lost.