background image

Ceiling Concealed Chilled Water 

Fan Coil Unit

Engineer Data

ED-FWW-VC-201607

Models:

 

 FWW200VC

 

 

 

 

FWW300VC FWW400VC FWW500VC

 

 

FWW600VC

 

  FWW700VC  FWW800VC  FWW1000VC

 

 

FWW1200VC

 

FWW1400VC

Air Flow:

 

340-2380m

3

/h

Содержание FWW200VC

Страница 1: ...Ceiling Concealed Chilled Water Fan Coil Unit Engineer Data ED FWW VC 201607 Models FWW200VC FWW300VC FWW400VC FWW500VC FWW600VC FWW700VC FWW800VC FWW1000VC FWW1200VC FWW1400VC Air Flow 340 2380m3 h ...

Страница 2: ...h them Warning Moving machinery and electrical power hazard May cause severe personal injury or death Disconnect and lock off power before servicing equipment Literature No ED FWW V 201501 Supersedes ED FWW VC 201607 Contents Nomenclature 2 Valve Nomenclature 3 Features 4 Specifications 5 Sound Data 6 Air Flow vs ESP Curve 7 Operating Limits 8 Water Flow Rate Pressure Drop Chart 9 Outlines and Dim...

Страница 3: ...m C without return air plenum E back return air plenum 5mm PE insulation F bottom return air plenum 5mm PE insulation Pipe Connection R facing air flow right hand L facing air flow left hand External Static Pressure 1 12 Pa 3 30 Pa 5 50 Pa Coil Type C 3 rows Unit Design SN Rated Air Volume CFM 1 CFM 1 7 m3 h DAIKIN Ceiling Concealed Horizontal Fan Coil Unit B back return air plenum D bottom return...

Страница 4: ...Way Valve Kit 3V 3 Way Valve Kit Union Size Omitted R3 4 4 R1 Pipe Connection R for Right hand unit L for Left hand unit E Export U Stick Made In China Power Supply A 220 240V 1Ph 50Hz K 208 230V 1Ph 60Hz Valve Type B with Ball Valve X without Ball Valve Strainer Type Y with Y Strainer X without Y Strainer ...

Страница 5: ...a for the heat exchanger to endure high pressures and prevent leakage High Efficiency Heat exchanger with the high quality mechanically expanded copper pipe and hydrophilic aluminum fins to ensure high efficiency Intensified air supply using a large air flow fan with a wide impeller to maximize the heat transfer performance Precise matching of the fan and motor to guarantee the maximum cooling cap...

Страница 6: ...ING CAPACITY W 3500 5330 6800 8400 9600 11100 13500 15800 18300 21500 Btu h 11942 18187 23203 28662 32757 37875 46064 53912 62442 73361 WATER FLOW RATE m3 h 0 37 0 58 0 72 0 88 1 02 1 14 1 41 1 67 1 95 2 29 USGPM 1 6 2 6 3 2 3 9 4 5 5 0 6 2 7 4 8 6 10 1 HEAD LOSS Cooling Pa 25 21 30 30 32 35 32 40 35 50 in wg 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 2 0 2 0 2 UNIT WEIGHT Without plenum kg 10 3 12 4 12 8 15 1...

Страница 7: ...8 908 1238 1288 1488 1638 in 17 24 24 72 26 69 29 83 33 77 35 74 48 73 50 70 58 57 64 47 WIDTH mm 196 in 7 71 THICKNESS mm 8 in 0 31 NOTES 1 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE 2 SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT Sound Data FWW VC Model FWW200VC FWW300VC FWW400VC FW...

Страница 8: ...Pa Air Flow m 3 h Air Flow m 3 h Air Flow m 3 h ESP Pa ESP Pa FWW1200 FWW1000 FWW800 FWW700 FWW600 FWW500 FWW400 FWW200 FWW300 FWW1200 FWW1000 FWW800 FWW700 FWW600 FWW500 FWW400 FWW200 FWW300 FWW1200 FWW1000 FWW800 FWW700 FWW600 FWW500 FWW400 FWW200 FWW300 ...

Страница 9: ...Operating Limits Operating Limits FWW V Water Circuit Max Water side pressure 1 6MPa Min Entering water temperature 3ºC cooling Power supply Operating voltage limits 10 Volt Operating frequency limits 2Hz ...

Страница 10: ... 6 0 7 0 8 0 9 1 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 2 1 2 2 2 3 WATER PRESSURE DROP kPa WATER FLOW m3 h WATER PRESSURE DROP CURVE 3 Rows Water Flow Rate Pressure Drop Chart FWW VC FWW700VC FWW500VC FWW300VC FWW400VC FWW200VC FWW1000VC FWW800VC FWW1200VC FWW600VC ...

Страница 11: ...r Of Fans MCW200V WITH BACK PLENUM TERMINAL BOX MOUNTING HOLE 4 10 16 CONDENSATE DRAIN R3 4 AIR VENT WATER SUPPLY CONNECTION Rc3 4 WATER RETURN CONNECTION Rc3 4 Model Standard Drain Pan Long Drain Pan Number Of Fans Standard Drain Pan Model Long Drain Pan Number Of Fans WITH BOTTOM PLENUM TERMINAL BOX MOUNTING HOLE 4 10 16 CONDENSATE DRAIN R3 4 AIR VENT WATER SUPPLY CONNECTION Rc3 4 WATER RETURN C...

Страница 12: ...R INSULATION GRADE B POWER SOURCE V Ph Hz 220 1 50 RATED INPUT POWER W 39 53 72 83 107 122 142 174 217 250 RATED RUNNING CURRENT A 0 18 0 24 0 33 0 38 0 49 0 56 0 65 0 80 1 00 1 19 POLES 4P 50Pa MOTOR INSULATION GRADE B POWER SOURCE V Ph Hz 220 1 50 RATED INPUT POWER W 46 62 80 95 112 131 168 200 237 290 RATED RUNNING CURRENT A 0 21 0 28 0 37 0 44 0 51 0 60 0 77 0 92 1 09 1 45 POLES 4P NOTES 1 ALL...

Страница 13: ... HF MF N 220V 50Hz YELLOW BROWN ORANGE YELLOW BROWN ORANGE BLUE BLACK BLACK BLACK BLACK BLUE MOTOR CAPACITOR MOTOR CAPACITOR FAN MOTOR 1 FAN MOTOR 2 Only unit 800 1200 have fan motor2 NOTE HF FAN SPEED HIGH MF FAN SPEED MEDIUM LF FAN SPEED LOW FIELD WIRING LF L ...

Страница 14: ...ding to the carrier with a formal claim Location Before installation please check the following There must be enough space for unit installation and maintenance Please refer to the unit s drawings and dimensions and fig 1 for the minimum distance between the unit and obstacle Please ensure enough space for piping connection and electrical wiring Please make sure that the hanging rods can support w...

Страница 15: ...ction Using suitable fittings as water pipe connections Refer to the specification The water inlet is on the bottom while outlet on top The connection must be concealed with rubberized fabric to avoid leakage Drainpipe can be PVC or steel The suggested slope of the drainpipe is at least 1 50 Wiring 1 Wiring connection must be done according to the wiring diagram on the unit 2 The unit must be GROU...

Страница 16: ...adjusting the water flow and for closing the water circuit when perform maintenance to the unit Y strainer protects unit from impurity increases the service life and insolating valves All parts of 2 way valve kit are indicated in the figure 1 For right pipe connection unit All parts of 3 way valve kit are indicated in the figure 2 For right pipe connection unit Figure 1 Figure 2 A Ball valve B Bra...

Страница 17: ...For right pipe connection unit Detail is as same as 2 way valve unit The valve kit has been pre assembled for easy installation Where needed the connections are pre coated with sealing material The connections are not tightened for easy adjustment After determining the final position of the valve kit tighten all connections to obtain water tightness 220 203 146 65 209 WATER RETURN CONNECTION Rc3 4...

Страница 18: ... 20 Rc3 4 3 way Valve 3 4 0 18 MC FCV2334G 20 Rc3 4 2 way Valve 3 0 0 18 Pipe Connection 1 Using suitable fittings as water pipe connections with reference to the outline and dimensions 2 The water inlet is on the bottom while outlet on top 3 The connection must be concealed with rubberized fabric to avoid leakage 4 Tightening torque should not be too high when connecting water pipes in order to a...

Страница 19: ...ectrical shock fire or explosion Read the User s Manual carefully before using this product The User s Manual provides important safety instructions and warnings Be sure to follow these instructions and warnings If you have any enquiries please contact your local importer distributor and or retailer Warning The air conditioners manufactured by Daikin Industries have received ISO 9001 series certif...

Отзывы: